Table 7. B6EM (FSHE) Minimum Heating Airflow Settings (CFM)

CABINET

NOMINAL ELECTIC HEAT KW

5

8

10

15

20

25

30

A

800

900

1000

1300

N/A

N/A

N/A

B

900

1000

1100

1300

1500

N/A

N/A

C

1000

1100

1200

1400

1600

1800

2000

NOTE: See Table 6 for appropriate switch settings for these airflows.

A-CABINET

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMINAL

CAPACITY

5

6

7

8

525

0

0

0

0

1.5 TON

560

0

0

0

1

600

0

0

1

0

625

0

0

1

1

700

0

1

0

0

2 TON

750

0

1

0

1

800

0

1

1

0

2.5 TON

850

0

1

1

1

875

1

0

0

0

890

1

0

0

1

930

1

0

1

0

950

1

0

1

1

1000

1

1

0

0

3 TON

1050

1

1

0

1

1125

1

1

1

0

1200

1

1

1

1

B-CABINET

C-CABINET

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMINAL

CAPACITY

CFM

SWITCH SETTINGS

(1 = ON, 0 = OFF)

NOMICAL

CAPACITY

5

6

7

8

5

6

7

8

525

0

0

0

0

1.5 TON

1100

0

0

0

0

3 TON

560

0

0

0

1

1200

0

0

0

1

3.5 TON

600

0

0

1

0

1250

0

0

1

0

650

0

0

1

1

2 TON

1300

0

0

1

1

4 TON

700

0

1

0

0

1350

0

1

0

0

750

0

1

0

1

1400

0

1

0

1

800

0

1

1

0

2.5 TON

1450

0

1

1

0

850

0

1

1

1

1500

0

1

1

1

875

1

0

0

0

1550

1

0

0

0

950

1

0

0

1

1600

1

0

0

1

5 TON

1050

1

0

1

0

3 TON

1650

1

0

1

0

1150

1

0

1

1

3.5 TON

1700

1

0

1

1

1250

1

1

0

0

1750

1

1

0

0

1350

1

1

0

1

4 TON

1800

1

1

0

1

1400

1

1

1

0

1900

1

1

1

0

1600

1

1

1

1

2000

1

1

1

1

Table 8. B6VM Recommended Cooling Airflow Settings