Table 7. b6em (fshe) minimum heating airflow, Settings (cfm), Table 8. b6vm recommended cooling airflow – Reznor B6BM Unit Installation Manual User Manual
Page 21: Settings, Lists the basic airflow values versus, Table 8

21
Table 7. B6EM (FSHE) Minimum Heating Airflow Settings (CFM)
CABINET
NOMINAL ELECTIC HEAT KW
5
8
10
15
20
25
30
A
800
900
1000
1300
N/A
N/A
N/A
B
900
1000
1100
1300
1500
N/A
N/A
C
1000
1100
1200
1400
1600
1800
2000
NOTE: See Table 6 for appropriate switch settings for these airflows.
A-CABINET
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMINAL
CAPACITY
5
6
7
8
525
0
0
0
0
1.5 TON
560
0
0
0
1
600
0
0
1
0
625
0
0
1
1
700
0
1
0
0
2 TON
750
0
1
0
1
800
0
1
1
0
2.5 TON
850
0
1
1
1
875
1
0
0
0
890
1
0
0
1
930
1
0
1
0
950
1
0
1
1
1000
1
1
0
0
3 TON
1050
1
1
0
1
1125
1
1
1
0
1200
1
1
1
1
B-CABINET
C-CABINET
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMINAL
CAPACITY
CFM
SWITCH SETTINGS
(1 = ON, 0 = OFF)
NOMICAL
CAPACITY
5
6
7
8
5
6
7
8
525
0
0
0
0
1.5 TON
1100
0
0
0
0
3 TON
560
0
0
0
1
1200
0
0
0
1
3.5 TON
600
0
0
1
0
1250
0
0
1
0
650
0
0
1
1
2 TON
1300
0
0
1
1
4 TON
700
0
1
0
0
1350
0
1
0
0
750
0
1
0
1
1400
0
1
0
1
800
0
1
1
0
2.5 TON
1450
0
1
1
0
850
0
1
1
1
1500
0
1
1
1
875
1
0
0
0
1550
1
0
0
0
950
1
0
0
1
1600
1
0
0
1
5 TON
1050
1
0
1
0
3 TON
1650
1
0
1
0
1150
1
0
1
1
3.5 TON
1700
1
0
1
1
1250
1
1
0
0
1750
1
1
0
0
1350
1
1
0
1
4 TON
1800
1
1
0
1
1400
1
1
1
0
1900
1
1
1
0
1600
1
1
1
1
2000
1
1
1
1
Table 8. B6VM Recommended Cooling Airflow Settings