Condensate drainage, Caution – Reznor B6BM Unit Installation Manual User Manual

Page 10

background image

10

• If the air handler is located in or above a living space

where damage may result from condensate overflow,

an auxiliary drain pan shall be installed under the unit.

A separate drain line should extend from the pan to a

conspicuous point and serve as an alarm indicating

that the primary drain is restricted. As an alternative to

a separate drain line, an approved water level indicator

or float switch device may be used to shut down the

unit in the event water is detected in the auxiliary pan.

• Install a single 5 inch trap in the condensate drain line

as close to the coil as possible. Make sure that the

top of the trap is below the bottom of the drain pan to

prevent the condensate from overflowing the drain pan.

NOTE: There must be only one trap in the drain line.

Using more than one trap may prevent drainage.

• Prime the trap with water. Insulate the drain if it is located

in an unconditioned space, and test the condensate line

for leaks. Consult local codes for additional restrictions

or precautions.

• During system checkout, inspect the drain line and

connections to verify proper condensate drainage.

8. Evacuate the system of moisture and non-condensables

to prevent low efficiency operation or damage to the

unit. The suggested range of evacuation is 350 - 500

microns.

9. Charge the system with refrigerant. Refer to the

outdoor unit installation manual for additional charging

instructions.

10. Check the system for leaks, including the lineset and

the brazed joints.

11. Replace all grommets and properly dispose of all

removed parts.

Condensate Drainage

CAUTION:

The air handler must be level to ensure proper

condensate drainage. An unlevel installation may

result in structural damage, premature equipment

failure, or possible personal injury.

• Methods for disposing of condensate vary according

to local codes. Refer to local codes or authority having

jurisidiction for restrictions and proper condensate

disposal requirements.

• The drain pan that is supplied with this air handler

contains a primary and secondary drain fitting. The

condensate is drained from the unit through two 3/4”

female pipe fittings located on the front side of the unit
as shown in

Figure 8

.

• The drain pan must be drained with field supplied tubing

or pvc pipe and adequately trapped. Both drain tubes

must have a minimum diameter of 3/4” and be trapped

separately.

IMPORTANT: Failure to install a trap may result in

condensation overflowing the drain pan, resulting in

substantial water damage to surrounding area.

• Route both lines to a suitable drain, avoiding sharp bends

and pinching of the lines. The drain should maintain a

minimum horizontal slope in the direction of discharge

of not less than 1” vertical for every 10 ft of horizontal

run.

3/4” Adapter w/

3/4” dia. hose barb

3/4” minimum dia.

PVC or flexible tubing

HORIZONTAL

UPFLOW

DOWNFLOW

NOTES:
1. The drain lines must maintain a downward slope to ensure proper

condensate drainage.

2. Each condensate drain must be trapped separately using a J-Trap or

field supplied loop.

Figure 8. Condensate Drainage Example