The coil fits over the discharge opening on the top of a Reznor

®

Model CAUA

heater. The heater should be in its final installed location before adding the

cased cooling coil. The heater must be level.

4.1 Place Coil on

top of the Model

CAUA Heater

4. Cooling Coil

Installation

Instructions

TABLE 3 -

Approximate

Weights of the

Cooling Coils

Read these instructions and become familiar with the installation requirements.

If you do not have knowledge of local requirements, check with the local gas

company or any other local agencies who might have requirements concerning

this installation.

Before beginning, make preparations for necessary supplies, tools, and man-

power. Installation should be done by an HVAC technician qualified in refriger-

ant system installation.

Verify that the package of parts required to install the heat section condensate

drain is either already installed or at the job site.

If specified, place field-supplied gasket material on the top of the heater where

the cabinet surfaces will have contact. The coil will "fit" with the line connection

holes in front or rear of the cabinet. Locate the openings and determine the

most efficient orientation. Lift the coil and place it on top of the heater.
Because of the cabinet design, there is no mechanical attachment required

between the heater and the cased cooling coil.
Verify that the heater and coil cabinet are level.

For CAUA 150 or 200

lbs

kg

ACUA 060 / Opt C060

83

38

ACUA 072 / Opt C072

86

39

ACUA 090 / Opt C090

105

48

For CAUA 250 or 300

lbs

kg

ACUB 090 / Opt C090

110

50

ACUB 120 / Opt C120

122

55

ACUB 150 / Opt C150

140

64

For CAUA 350 or 400

lbs

kg

ACUC 120 / Opt C120

176

80

ACUC 150 / Opt C150

180

82

ACUC 180 / Opt C180

188

85

4.2 Thermostatic

Expansion

Valves

Optional

Cased

Cooling

Coil

Model

CAUA

FIGURE 2 -

Model CAUA

Heater with

Cooling Coil

Locate the shipped-loose TEV Kit components and verify them by Size with the

list in

TABLE 4 and with the unit rating plate.

Identify the components that are required for each circuit and prepare to assem-

ble. Refer to the valve manufacturer's instructions for installation information.

When brazing the valve, wet wrap the valve body, but do not allow moisture to

enter the tubing. Braze with the flame pointed away from the valve.
Position the

outlet of the Circuit A thermostatic expansion valve toward the

distributor connection on the bottom liquid line. If a reducer is required, position

it between the distributor and the outlet of the valve.

If there is a reducer, attach the reducer to the distributor connection and the

outlet of the valve to the reducer.

If there is no reducer, attach the outlet of the valve to the distributor

connection.

Repeat the same procedure to install the thermostatic expansion valve in

Circuit B (the top liquid line).