Reznor VPS Unit Installation Manual User Manual
Page 12
12
1.8 Technical Details -
Table 5
No of Injectors
1
Gas Connection
½” N.P.T
Electrical Supply
120 volt 1 phase 60Hz
Vent size (in)
4” or 6” (101mm or 152mm)
Unitary Fan Motor Details
120 volt 1 phase 60Hz
Current Rating
1.2A MAX
Ignition
Electronic Program Start up with Spark Ignition
MODEL
Natural Gas LP Gas
Min. Heater
Length
Max. Heater
Length
Min. Heater
Length
Max. Heater
Length
BTU/Hr
BTU/Hr
S ft (m)
S ft (m)
U ft (m)
U ft (m)
60
60,000
60,000
20 (6.1)
40 (12.1)
20 (6.1)
40 (12.1)
80
80,000
80,000
20 (6.1)
40 (12.1)
20 (6.1)
40 (12.1)
100
100,000
100,000
30 (9.1)
50 (15.2)
40 (12.1)
40 (12.1)
125
123,500
125,000
40 (12.1)
60 (18.3)
40 (12.1)
60 (18.3)
150
150,000
150,000
40 (12.1)
70 (21.3)
40 (12.1)
60 (18.3)
170
169,000
169,000
50 (15.2)
80 (24.4)
60 (18.3)
80 (24.4)
200
200,000
N/A
50 (15.2)
80 (24.4)
60 (18.3)
80 (24.4)
N/A
USA
Natural Gas 0- 2000 ft (0-610m)
Size
60 80 100 125 150 170 200
“WC
4.2 3.5 3.5 4.1
4.2
3.4 3.5
USA
LP Gas 0- 2000 ft (0-610m)
Size
60 80 100 125 150 170 200
“WC
6.0 5.2 8.2 6.6
7.0 5.7 N/A
USA
Natural Gas 2001- 4000 ft (611-1220m)
Size
60
80 100 125 150 170 200
“WC
4.0 3.3 3.3
3.9
4.0
3.2
3.3
USA
LP Gas 2001- 4000 ft (611-1220m)
Size
60 80 100 125 150 170 200
“WC
5.8 5.0 8.0 6.4 6.8
N/A
CANADA
Natural Gas 0- 2000 ft (0-610m)
Size
60 80 100 125 150 170 200
“WC
4.2 3.5 3.5 4.1 4.2
3.4
3.5
CANADA
LP Gas 0- 2000 ft (0-610m)
Size
60
80 100 125 150 170 200
“WC
6.0 5.2 8.2 6.6 7.0 5.7 N/A
CANADA Natural Gas 2001- 4500 ft (611-1370m)
Size
60 80 100 125 150 170 200
“WC
4.0 3.3 3.3 3.9 4.0
3.2
3.3
CANADA
LP Gas 2001- 4500 ft (611-1370m)
Size
60 80 100 125 150 170 200
“WC
5.8 5.0 8.0 6.4 6.8
N/A
Appliances can be installed up to 10,000ft in the USA. Altitude conversion kits are available on request.