Figure 7.a vertical venting – Reznor VPS Unit Installation Manual User Manual

Page 11

background image

11

Figure 7.b Horizontal Venting.

Figure 7.c Fresh Air Ducted Intake.

Figure 7.d Wall Terminal Intake Kit.

NOTE: The vent
terminal should be
installed so as to be in
the same atmospheric
pressure zone as the
combustion air inlet of
the appliance

REFLECTOR

END OF RADIANT TUBE

VENT ADAPTOR ELBOW

12'-0" (3.66m)

12'-0" (3.66m)

(APPROXIMATE

MAXIMUM DIMENSIONS)

CODE APPROVED VENT
THROUGH ROOF

SEAL

S

UP

PL

IE

D B

Y

OTHERS

ROOF

4" (101mm) O.D. OR

HIGH TEMPERATURE SILICONE

SEAL JOINTS WITH

REQUIRED ONLY FOR 6" (152mm) DIA. VENT

4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAPTER

6" (152mm) O.D. FLUE

ALUMINUM

RADIANT
TUBE

REFLECTOR

4" (101mm) TO 6" (152mm) DIA. ALUMINUM ADAPTER

TERMINAL

6" (152mm)

COLLAR

SEAL JOINTS WITH

HIGH TEMPERATURE

WALL

REQUIRED ONLY FOR 6" (152mm) DIA. VENTS

ALUMINUM 4" (101mm) O.D. MAXIMUM LENGTH = 12'-0" (3.66m)
ALUMINUM 6" (152mm) O.D.MAXIMUM LENGTH = 25'-0" (7.62m)
(PLUS A MAXIMUM OF 2 x 90° BENDS

END OF

SUPPLIED BY OTHERS

COUPLER

SILICONE

INLET WITH
BIRD SCREEN

36"

(91

4mm) MIN CENT

ER

S

ALUMINUM 4" (101mm) O.D. PIPE

CLAMPS

4" (106mm) O.D. FLEXIBLE DUCT

BURNER

MAX LENGTH = 25'-0" (7.62m) WITH 2-90° LONG RADIUS BENDS

INLET WITH

6" (152mm)

SEAL JOINTS WITH

SILICONE OR DUCT TAPE

WALL

BIRD SCREEN

TERMINAL

36" (914m

m) MIN CENTERS

4.25” (108mm) O.D FLEXIBLE DUCT

APPROVED CAT III VENT PIPE

APPROVED CAT 3 VENT PIPE

ENSURE ALL JOINTS ARE

SEALED

Figure 7.a Vertical Venting.

CAT III ADAPTER

VENT CAT III ELBOW

ELBOWS

WITH TWO– 90° ELBOWS