Microtel Series 1000EX User Manual
Page 41

MICROTEL Series 1000EX Dialer
35
z I/O Channel Telephone List A list of selected phone numbers an I/O channel will
call repeatedly upon alarm until the alarm is acknowledged.
*cc4
Review I/O c Telephone selections
**cc4tt* Program I/O c Telephone selections
tt is a list of 0 to 9 telephone indexes.
Examples- Command:
**0140208*
Response: Channel one telephone list is two and eight.
-and-
Command: **024*
Response: Channel two telephone list is none.
NOTE: When the channel’s telephone list is none, it will skip over this channel
when looking for the highest priority channel in alarm.
z I/O Channel Status/Clear Counters A spoken status message for I/O channel c
only. The data spoken is dependent upon the user-configured report format for
channel c. This will also speak the alarm condition for that channel. It will specify if
the channel is currently in alarm, has an alarm that has been acknowledged, or is now
normal (had an unacknowledged alarm that has since cleared).
*cc0*
Report I/O channel c status
**cc0*
Reset and Report I/O channel counter and runtime
Example voice messages-
Digital Input Type
Channel one normally open digital input is Open.
Digital Output Type Channel two digital output is ON.
Counter
Input
Channel one normally open digital input zero
counts.
Analog
Input
Channel four analog input is at seven five point
zero
percent.
Power
Fail
Channel 9 Power Normal.
Example- Command:
**010*
Response:
Channel one normally open digital input zero counts
runtime is zero.