Microtel Series 1000EX User Manual
Page 31

MICROTEL Series 1000EX Dialer
25
Basic System Information Overview
NOTE: All commands and inquiries terminate with ‘*’ (single star).
The following commands configure and report the current values for the overall system
level operations of the Series 1000EX. These settings include:
Section Current
Setting
Change
Setting
Meaning
Voice System Name
0*01* 0**01*~
User defined Voice System Name for the
Dialer
Call Spacing Time
0*02* 0**02MM* Time in minutes the dialer waits after
making an answered outgoing call before
making another one
Ring Count
0*03* 0**03nn*
Waits nn rings before answering an
incoming call
Access Code
0*04* 0**04nnnn* Code to get access to the Dialer during a
callin or callout
Message Repeat
Count
0*05* 0**05nn*
Number of times the Dialer will repeat the
alarm messages for a callin or callout
Voice Interaction
Delay
0*06* 0**06n*
Delay time between entering a command
and the dialer responding to this command
Callback
Acknowledge
0*08* 0**08n*
Enabling Callback Acknowledge.
n=1 Enables it. n=0 Disables it
Snooze Delay Time
Interval
0*74* 0**74
DDHHMM*
The delay after which the Dialer will re-arm
an acknowledged alarm so that alarm will
again generate callouts
System Telephone #
0*100* 0**100p** The Dialer’s telephone number (Required
for faxes to comply with FCC
Regulations)
A Glossary of Dialer Terminology that defines these parameters with respect to the
Series 1000EX operation is provided in the Appendix.