beautypg.com

Maxim Integrated 6613_PSU_1+1S_URT_v1_00 User Manual

Page 30

background image

6613_PSU_1+1S_URT_V1_00 Firmware Description Document

UG_6613_040

30

Rev. 1.0

CE

Parameter

Location(

hex)

LSB

Default

Comment

Example

WRATE

0F

Kh =

VMAX A *

IMAX A /

(WRATE *

X)

1.6826E+0

1 WattSec

+4860

Controls the

number of pulses

that are generated

per measured Wh

and VARh

measurements.

]0F=+4860

Kh = 0.32 * Wh / pulse with X = 6/64,

VMAX =600 V

and

IMAX = 52 A

Reserved

10

Reserved

SAG

Threshold

11

VMAX A

*4.2551E-

07 (Vpk)

+168225

The voltage

threshold for SAG

warnings. The

default value is 80

Vpk if VMAX = 600

V.

]11=+313350

80 Vpk SAG Threshold.

QUANTA

12

VMAX A *

IMAX A *
1.8541E-

10 (Watt)

0

Compensation

added to the Watt
calculation. Used

for compensation at

low current levels.

Keep below

10000d.

Unused

13-15

QUANT IA

16

(IMAX A)

2

*

4.6351E-11

(A

2

)

0

IA input

compensation

added for input

noise and

truncation in the

squaring calculation

for I

2

. Used for

compensation at

low current levels.

Keep below

10000d.

Unused

17

AC Cycle

Count

18

1

+4

Number of AC

cycles for

accumulation

interval (min=4)

To changes accumulation interval to 10

AC cycles:

]18=+10

Note: Set value of AC cycles between 4

and 100/120 (for 50/60Hz respectively).

Gain Adjust

19

16384 is

the default

and is a

gain of 1.

+16384

32767 is max giving

a

gain of 2.

To increase all channels equally by 1%

scale the nominal number, 16384 by

1/(1-0.01). Number to be entered would

be 16549:

]19=+16549

To decrease all channels 1% scale the

nominal number, 16384 by 1/(1+0.01).

Number to be entered would be 16222:

]19=+16222

Reserved

1A-1B

Reserved

Reserved