Maxim Integrated 6613_PSU_1+1S_URT_v1_00 User Manual
Page 27
UG_6613_ 040
6613_PSU_1+1S_URT_V1_00 Firmware Description Document
Rev. 1.0
27
MPU
Parameter
Location
(hex)
LSB
Default
Comment
Example
Frequency
Minimum
Threshold
D2
0.01Hz
+59.00
Minimum Frequency Alarm
Threshold. A frequency below
this threshold will set the alarm
(bit 2 of the Alarm Status
Register).
If the minimum frequency
threshold is to be changed
to 59.50 Hz then enter the
following:
>)D2=+59.50
Frequency
Maximum
Threshold
D3
0.01Hz
+61.00
Maximum Frequency Alarm
Threshold. A frequency above
this threshold will set the alarm
(bit 3 of the Alarm Status
Register).
If the maximum frequency
threshold is to be changed
to 60.50 Hz then enter the
following:
>)D2=+60.50
SAG Voltage
Alarm
Threshold
D4
mVpk
+80.0
Sets an alarm (bit 4 of the Alarm
Status Register) if voltage drops
below the SAG threshold.
Min Voltage
Alarm
Threshold
D5
mVrms
+100.000
Minimum voltage level selected to
flag user (bit 5 of the Alarm Status
Register).
To change the minimum
voltage threshold from the
40 Volt default to 80 Volts:
)D5=+80.000
Peak Voltage
Alarm
Threshold
D6
mVrms
+140.000
Peak voltage setting that user
wishes to flag (bit 6 of the Alarm
Status Register).
To change the peak voltage
threshold from the default
407.3 Volts to 280 Volts:
)D6=+280.000
Unused
D7-D8
–
Peak IA
Alarm
Threshold
D9
mArms
+15.000
Maximum Current measured on
the IA channel above which a flag
must set (bit 8 of the Alarm Status
Register).
If the peak current
threshold is to be changed
from the default value of 15
Amps to 30 Amps then set
as follows:
)D9=+30.000