SECTION 15.
Trouble Shooting
15A. S9301A Control Module
NORMAL SEQUENCE
FAILURE TO COMPLETE THIS CYCLE
Event
Control Funtion
Verified
Envent Confirmed
Light Event
Unconfirmed
Action for
Diagnosis
A. Power switch on
Integrated boiler control
(S9301A)
Green "POWER" light on.
Note: If internal pump is
running unit may be in
lockout. Reset power
switch.
1. No 120 VAC supply
1. Read voltage between
black & white wires at back
of (120 VAC) plug
2. Defective 24 VAC
transformer
2. Read voltage between
yellow wires at back of
(VAC 24XFMR) plug
3. Defective S9301A
module
3. Replace S9301A part
#2400-224
B. Prepurge (if low limit or
Thermostat calling)
2 - 17) secs)
1. Internal Pump Starts
Red "PURGE" light on.
Note: If unit in purge mode
without light, stack switch is
not proving air flow.
1. Internal pump defective
or air bound
1. Check for 120 VAC at
module pins marked
circulator (opposite brown
and white)
2. Low limit (HW-only),
operating control, safety
limit, system pressure
switch, stack switch
2. Defective low limit,
operating control, safety
limit or differential presssure
switch
2. Jump control wires, one
control at a time to identify
open circuit control, no
continuity.
3. Blower starts
3. Defective inducer blower
3. Check for 120 VAC at
module pins marked inducer
(opposite gray and white
wires)
C. Igniter heats up and
remains on (17 - 39 sec)
Igniter via S9301A
Red "IGNITER" light on
Red "PURGE" light off
Blower continues to run
Igniter does not heat up -
look for heat up at igniter
base
Check for 120 VAC at pins
marked IGNR (blue wires)
during igniter light "on"
D. Gas valve energized
(37 - 43 secs)
Gas valve opens
Red "VALVE/FLAME" light
on.
1. Stack switch does not
confirm air flow.
2. Gas valve has short.
Check for 24 VAC between
orange and yellow wires on
gas valve when red "VALVE
/ FLAME" light is on
E. Ignitor off (39 sec)
Gas valve energized
(39 - 43+ sec)
Igniter, air & gas source
Igniter monitors flame via
flame rectification to ground
Unit transfer to purge 12-15
secs after "valve / flame"
light is on and repeats
sequence
See trouble shooting
section under "cross
contamination" & "short
cycling" in service manual