Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual
Page 34
Page 34
LAARS Heating Systems
Figure 29. Red "Valve/Flame" Light Flashing (You Must Complete Figure 24 First).
RESET BOILER BY INTERUPTING POWER FOR 15
SECONDS - WHEN "VALVE/FLAME" LITE LIGHTS
IS THERE 24 VAC BETWEEN ORANGE AND
YELLOW WIRES ON GAS VALVE AND/OR DOES
GAS VALVE CLICK?
TURN ON VALVES, FILL LP TANK ON LP
UNIT. RESET BOILER BY SWITCHING
POWER OFF FOR 15 SECONDS. RUN
THROUGH TWO TO THREE CYCLES
CHECK WIRES TO GAS VALVE
DOES BURNER IGNITE AND
APPEAR TO RUN PROPERLY?
NUISANCE LOCKOUT CAUSED FLASHING
LITE - CHECK COMBUSTION
CHECK IGNITER-
IGNITER OK?
50 - 150 OHMS,
NO CRACKS.
REPLACE
INTEGRATED
BOILER
CONTROL
P\N 2400-224
CORRECT
WIRING
REPLACE
IGNITER
REPLACE INTEGRATED BOILER CONTROL P/N 2400-224
INSTALL
CORRECT
ORIFICES
BOILER CYCLES THROUGH THREE CYCLES AFTER
RESETTING AND “VALVE” LITE FLASHES
CHECK GAS AND AIR ORIFICE
FOR PROPER SIZE
REPLACE GAS VALVE
ARE GAS VALVES AND GAS METER TURNED ON.
IS THERE GAS IN LP TANK (LP UNITS).
YES
YES
YES
NO
OK
FAULTY
NO
INCORRECT
CORRECT
NO
Р
Р
Р
Р
Р
Р
Р
Р
Р
Р
CHECK FOR GAS FLOW.
IS METER MOVING?
(GAS PRESSURE IS OK)
Р
Р
YES
NO
Р
Р
Р
YES
NO
OUT OF
PRODUCTION