RATE CALIBRATION
RATE CALIBRATION is probably not necessary. The software initially
expects STANDARD hardware. However, if you are using an auger feeder
on a model with four dispense valves, or a 1/2 inch auger instead of a
1" auger, the software will take 10 or 20 cycles to adjust to correct
operation. This slows down the process for a short time, but does not
effect accuracy.
If your hardware is STANDARD, or
you prefer letting the system SELF ADJUST,
you may:
+---------------------------------------------------+
¦ ¦
¦ PROCEED TO: NORMAL OPERATION NEXT PAGE ¦
¦ ¦
+---------------------------------------------------+
To perform a RATE CALIBRATION:
Have all HOPPERS LOADED with enough material to run for several cycles
without running out.
Have the "OFF AT END OF CYCLE" and "PAUSE" switches DOWN.
Press: * Display will say: (PASSWORD)
Press: 22222 Display will say: (P x)
If your system has auger feeders, operate them briefly to ensure they
are fully primed. To do so:
Press: OPER Display will say: (OPERATE )
Press: COL Run until auger is dispensing.
Press: ADD Run until auger is dispensing.
Press: DUMP This will empty the weigh bin.
Now you can CALIBRATE EACH material.
To do so:
Press: CAL Display will say: (CALIBRATE)
Press: REG REGRIND will calibrate itself.
For each material, press CAL followed by the proper component key.
Each time a dispense will occur, followed by weighing, followed by
a dump to empty the weigh bin.
Press: EXIT when all calibrations are done.
YOU ARE NOW READY FOR ACCURATE PRODUCTION BLENDING.
+---------------------------------------------------+
¦ ¦
¦ PROCEED TO: SPECIAL INSTRUCTIONS NEXT PAGE ¦
¦ ¦
+---------------------------------------------------+