Table 2 — 38AUQ*07-12 Piping Recommendations (Single-Circuit Unit)

CHECK VERTICAL SEPARATION — If there is any vertical

separation between the indoor and outdoor units, check to

ensure that the separation is within allowable limits. Relocate

equipment if necessary.
PROVIDE SAFETY RELIEF — If local codes dictate an

additional safety relief device, purchase locally and install

locally. Installation will require the recovery of the factory

shipping charge before the factory tubing can be cut and the

supplemental relief device is installed.
REFRIGERANT LINE SIZING — Consider the length of

the piping required between the outdoor and indoor units. The

maximum allowable line length is 100 ft (30.5 m). See Table 2.

Refrigerant vapor piping should be insulated.

Table 3 — Maximum Vertical Separation*

*Vertical distance between indoor and outdoor units.

INSTALL FILTER DRIER(S) AND MOISTURE

INDICATOR(S) — Every unit MUST have a bi-directional

filter drier in the liquid line. Locate the filter drier at the indoor

unit, close to the evaporator coil’s thermal expansion valve

(TXV) inlets.
38AUQ units include one Puron-duty filter drier, shipped in

cartons attached to the unit basepan. Remove the filter drier

and prepare to install in the liquid line at the evaporator coil.

Do not remove connection fitting plugs until ready to connect

and braze the filter drier into the liquid line position.

Table 4 — Puron-duty Filter Drier(s)

Installation of liquid line moisture indicating sightglass in each

circuit is recommended. Locate the sightglass(es) between the

outlet of the filter drier and the TXV inlet.
Refer to Table 5 for recommendations on refrigeration

specialties.
Select the filter drier for maximum unit capacity and minimum

pressure drop. Complete the refrigerant piping from the indoor

unit to the outdoor unit before opening the liquid and suction

lines at the outdoor unit.

R-410A

Equivalent Length

Ft

0-38

38-75

75-113

113-150

Model

Nominal Capacity

Length Linear

Length Equiiv

0-25

0-38

25-50

38-75

50-75

75-113

75-100

113-115

38AUQ*07

Liquid Line

3

/

8

3

/

8

3

/

8

1

/

2

3

/

8

1

/

2

Max Lift

Cool

Heat

25

25

50

50

48

46

75

60

39

31

100

60

Suction Line

7

/

8

7

/

8

1-

1

/

8

1-

1

/

8

Charge (lbs)

17.8

18.8

20.3

22.6

21.4

24.5

38AUQ*08

Liquid Line

1

/

2

1

/

2

1

/

2

1

/

2

Max Lift

Cool

Heat

25

25

50

50

75

60

100

60

Suction Line

7

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

Charge (lbs)

20.9

23.0

24.9

26.8

38AUQ*12

Liquid Line

1

/

2

1

/

2

1

/

2

1

/

2

5

/

8

Max Lift

Cool

Heat

25

25

50

50

75

60

85

60

100

60

Suction Line

7

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

1

/

8

1-

3

/

8

Charge (lbs)

26.8

28.8

30.7

33.4

37.2

Legend:
Length Equiv

Equivalent tubing length, including effects of refrigeration specialties devices

Liquid Line

Tubing size, inches OD.

Max Lift

Cooling
Heating

Maximum liquid lift at maximum permitted liquid line pressure drop

• Indoor unit ABOVE outdoor unit

• Indoor unit BELOW outdoor unit

Suction Line

Tube size, inches OD

Charge

Charge Quantity, lbs. Calculated for both liquid line sizes (where applicable), but only with larger
suction line size (where applicable)

NOTE:

For applications with linear length greater than 100 ft (30.5 m), contact your local Carrier representative.

IMPORTANT: A refrigerant receiver is not provided

with the unit. Do not install a receiver.

UNIT 38AUQ

UNIT 40RUQ

DISTANCE FT (M)

Unit 38AUQ

Above Unit 40RMQ

07

07

50 (15.2)

08

08

60 (18.3)

12

12

60 (18.3)

Model-Size

Qty

Liquid

Line OD

Desiccant

Volume

Part

Number Ref

38AUQ*07

1

3

/

8

-in

8 cu. in.

KH43LG091

38AUQ*08

1

1

/

2

-in

16 cu. in.

KH43LG085

38AUQ*12

1

1

/

2

-in

16 cu. in.

KH43LG085