Table 8 — Electrical Data — 38AUQ*07-12 60 Hz Units

LEGEND

UNIT

SIZE

38AUQ

FACTORY-

INSTALLED

OPTION

NOMINAL

VOLTAGE

VOLTAGE

RANGE

COMPRESSOR

FAN MOTORS

POWER

SUPPLY

V-Ph-Hz

MIN

MAX

RLA

LRA

FLA (ea)

QTY

MCA

MOCP

*07

NONE OR DISCONNECT

208/230-3-60

187

253

19.0

123

1.5

2

26.8

45

CONVENIENCE OUTLET

31.6

50

NONE OR DISCONNECT

460-3-60

414

506

9.7

62

0.9

2

13.9

20

CONVENIENCE OUTLET

16.1

25

NONE OR DISCONNECT

575-3-60

518

633

7.4

50

0.6

2

10.5

15

CONVENIENCE OUTLET

12.2

15

*08

NONE OR DISCONNECT

208/230-3-60

187

253

25.0

164

1.5

2

34.3

50

CONVENIENCE OUTLET

39.1

60

NONE OR DISCONNECT

460-3-60

414

506

12.2

100

0.9

2

17.1

25

CONVENIENCE OUTLET

19.3

30

NONE OR DISCONNECT

575-3-60

518

633

9.0

78

0.6

2

12.5

20

CONVENIENCE OUTLET

14.2

20

*12

NONE OR DISCONNECT

208/230-3-60

187

253

30.1

225

1.5

2

40.6

60

CONVENIENCE OUTLET

45.4

60

NONE OR DISCONNECT

460-3-60

414

506

16.7

114

0.8

2

22.5

30

CONVENIENCE OUTLET

24.7

30

NONE OR DISCONNECT

575-3-60

518

633

12.2

80

0.6

2

16.5

25

CONVENIENCE OUTLET

18.2

30

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA —

Minimum Circuit Amps

MOCP —

Maximum Overcurrent

Protection

NEC

National Electrical Code

RLA

Rated Load Amps

Units are suitable for use on electrical systems where voltage supplied to

the unit terminals is not below or above the listed limits.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the NEC,

Article 440.

2. Motor RLA and LRA values are established in accordance with Underwriters’

Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.

4. Convenience outlet is available as a factory-installed option and is 115-v,

1 ph, 60 Hz.

5. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is

greater than 2%. Use the following formula to determine the percentage

of voltage imbalance.

Example: Supply voltage is 208/230-3-60

AB = 224 v
BC = 231 v
AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

3

3

=

227

Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

227

= 1.76%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

% Voltage Imbalance

= 100 x

max voltage deviation from average voltage

average voltage