COMFORT ALERT DIAGNOSTIC

MODULE

The Comfort Alert Diagnostic Module (CADM) monitors and

analyzes data from the Copeland Scroll

®

three-phase compres-

sor and the thermostat demand. The CADM also provides a

3-minute anti-recycle time delay to compressor cycling.
The CADM detects causes for electrical and system related

failures. Flashing LEDs communicate the Alert codes to guide

service technicians in accurately and quickly troubleshooting

the system and determining root cause for the failure.
Inputs to the CADM include 24-vac power, demand signal Y,

compressor contactor coil (common side) and compressor

power leads (from the compressor contactor).

Control of the compressor contactor coil is through a contact

between terminals P and C.
Communications of status and alert conditions is through three

LEDs located on the top edge of the module housing (see

Fig. 30): POWER (green), ALERT (yellow), and TRIP (red).
The POWER LED indicates the presence of control power to

the CADM.

Fig. 30 — CADM Housing/LED Locations

The ALERT LED indicates an abnormal condition exists in the

system through a flash code. The ALERT LED will blink a

number of times consecutively, pause and the repeat the

process. The number of blinks, defined in Table 14, correlates

to a particular abnormal condition; troubleshooting tips are

provided for each Alert code. Reset of the ALERT may be

automatic or manual. If the fault condition causing the Alert is

self-corrected, the Alert code will be removed and the CADM

will automatically reset and allow the system to restart

normally. Manual reset for lockouts requires that main power

to the 38AUQ unit be recycled after the cause for the Alert

condition has been detected and corrected.
The TRIP LED indicates either a time-delay period is currently

active (RED LED is blinking) or the module has locked out the

compressor (RED LED is on steady). A lockout condition will

occur for some faults as identified in Table 14. Reset of the

TRIP LED requires that unit main power be recycled after the

loss of power to the compressor condition has been detected

and corrected.
Simultaneous Blinking of YELLOW and RED LEDs indicates

control power input to the CADM is low. Check control circuit

transformer and wiring.
Troubleshooting the CADM Wiring – Flashing LEDs also

indicate wiring problems to the CADM. See Table 15 for

discussion of additional LED flash codes and troubleshooting

instructions.

Input

Terminal Voltage

Control Power

R

24-V

Control

Common

C

24-V

Demand

Y

24-V

Contactor Coil

P

24-V

Compressor T1

T1

Line

Compressor T2

T2

Line

Compressor T3

T3

Line

POWER
(GRN)

ALERT
(YEL)

TRIP
(RED)