Defrost Thermostats

These are temperature switches that monitor the surface tem-

perature of the outdoor coil circuits. These switches are mount-

ed on the liquid tube exiting the outdoor coil heating circuits.

These switches close on temperature drop at 30°F (-1°C) and

reset open on temperature rise at 80°F (27°C).

Indoor Fan Off Delay

The DFB can provide a 30 sec delay on Indoor Fan Off if the

thermostat's fan selector switch is set on AUTO control. DIP

Switch SW3 on the DFB selects use of the fan off time delay

feature. Setting SW3 in the OPEN position turns the Fan Off

Delay feature on; setting SW3 in the CLOSED position dis-

ables this feature. The delay period begins when Y1 demand or

W1 demand by the space thermostat is removed.

Defrost Speedup Functions

The DFB permits the servicer to speed-up the defrost cycle.

There are two speed-up sequences: relative speed-up and an

immediate forced defrost. Speed-up sequences are initiated by

shorting jumper wires JMP17 and JMP18 together (see

Fig. 22); use a straight-edge screwdriver.
Shorting the jumpers for a period of 1 to 3 secs reduces the de-

frost timer periods by a factor of 0.1 sec/minute. (For example,

the 90 min run period is reduced to 9 secs.) The DFB will step

the unit through a Heating cycle and a Defrost cycle using

these reduced time periods. This mode ends after the Defrost

cycle.
Shorting the jumpers for a period of 5 to 20 secs bypasses the

remaining continuous run period and places the unit in a

Forced Defrost mode. If the controlling DFT is closed when

this mode is initiated, the unit will complete a normal defrost

period that will terminate when the controlling DFT opens or

the 10 minute defrost cycle limit is reached. If the controlling

DFT is open when this mode is initiated, the Defrost cycle will

run for 30 secs. Both modes end at the end of the Defrost cycle.