Interlogix NX-8 User Manual
Page 21

NX-8 Control
21
NOTE: To “null” a zone, program the zone in “Partition Select” as zero (0) in all partitions and do not
use end-of-line resistors.
LOCATION 25 - ZONES 1-8 ZONE TYPE (8 segments, numerical data)
Location 25 contains the Zone Type for zones 1-8. Segment 1 is for zone 1, and Segment 8 is for zone 8.
Default Zone Types are found in the table on page 20. To customize a Zone Type, see page 35.
LOCATION 26 - PARTITION SELECT, ZONES 1-8 (8 segments, feature selection data)
Location 26 is used to select the partition(s) that zones 1 - 8 reside in. A zone may reside in any combination of the 8
partitions. If a burglary zone resides in more than 1 partition, it will only be active when all partitions it resides
in are armed. A zone that resides in more than 1 partition will be reported to its lowest partition number.
Location 26 has 8 segments. Segment 1 corresponds to zone 1, and Segment 8 corresponds to zone 8.
Segments 1 - 8:
1 = Partition #1
2 = Partition #2
3 = Partition #3
4 = Partition #4
5 = Partition #5
6 = Partition #6
7 = Partition #7
8 = Partition #8
LOCATION 27 - ZONES 9-16 ZONE TYPE (8 segments, numerical data)
Location 27 contains the Zone Type for zones 9 -16. Segment 1 is for zone 9, Segment 8 is for zone 16. Default
Zone Types are found in the table on page 20. To customize a Zone Type, see page 35.
LOCATION 28 - PARTITION SELECT, ZONES 9-16 (8 segments, feature selection data)
Location 28 is used to select the partition(s) that zones 9-16 reside in. A zone may reside in any combination of the 8
partitions. If a burglary zone resides in more than 1 partition, it will only be active when all partitions are
armed. A zone that resides in more than 1 partition will be reported to its lowest partition. Location 28 has 8
segments. Segment 1 corresponds to zone 9 and Segment 8 corresponds to zone 16.
Segments 1 - 8:
1 = Partition #1
2 = Partition #2
3 = Partition #3
4 = Partition #4
5 = Partition #5
6 = Partition #6
7 = Partition #7
8 = Partition #8
LOCATION 29 - ZONES 17-24 ZONE TYPE (8 segments, numerical data)
Location 29 contains the Zone Type for zones 17-24. Segment 1 is for zone 17, Segment 8 is for zone 24. Default
Zone Types are found in the table on page 20. To customize a Zone Type, see page 35.
LOCATION 30 - PARTITION SELECT, ZONES 17-24 (8 segments, feature selection data)
Location 30 is used to select the partition(s) that zones 17-24 reside in. A zone may reside in any combination of the
8 partitions. If a burglary zone resides in more than 1 partition, it will only be active when all partitions are
armed. A zone that resides in more than 1 partition will be reported to its lowest partition. Location 30 has 8
segments. Segment 1 corresponds to zone 17 and Segment 8 corresponds to zone 24.
Segments 1 - 8:
1 = Partition #1
2 = Partition #2
3 = Partition #3
4 = Partition #4
5 = Partition #5
6 = Partition #6
7 = Partition #7
8 = Partition #8