Chapter 1
Concord Express Installation Instructions
3
• RF TX TIMEOUT set to 24 hours
• EXTENDED DELAY set to off
• TWO TRIP ERROR set to off
• ALARM VERIFY set to off
• DISABLE TROUBLE BEEPS set to off
• SYSTEM TAMPER set to on
Household Fire Warning System (UL 985)
Basic system plus:
• Hardwire Smoke Detector:
System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, or 2400TH
learned into Sensor Group 26 Sentrol (ESL) models 429AT, 521B, or 521BXT
learned into sensor group 26
• Wireless Smoke Sensor 60-506-319.5 or 60-645-95 learned into sensor
group 26
• IMMEDIATE TROUBLE BEEPS set to on
• UL 98 OPTIONS set to on
• RECEIVER FAILURE set to on
• SIREN VERIFY set to on
• RF TX TIMEOUT set to 4 hours
• ALARM VERIFY set to off
• DISABLE TROUBLE BEEPS set to off
UL 1023 & 985 24-Hour Backup
For 24-hour backup, the total current draw for all connected devices is limited to
90 mA continuous using a 4.0 AH battery.
SIA System Requirements
Note
: UL requirements take priority over SIA requirements.
SIA system requirements are the same as those described for a UL Listed Basic
System on page 1, plus:
• If multiple annunciation is required, use Hardwire Siren part no.13-046.
SIA Setting Requirements
The following table describes programming requirements to meet ANSI-SIA CP-
01.