Wiring the fault alarm contact, Contact 9, Industrial switch – Interlogix DSGH Series User Manual
Page 13
Chapter 2: Installation
GE-DSG-8 DSGH-5 and 8 Ethernet Switch User Manual
9
Wiring the Fault Alarm Contact
The fault alarm contacts are in the middle of the terminal block connector as the
picture shows below. Inserting the wires, the Industrial Gigabit Ethernet Switch will
detect the fault status of a power failure, or port link failure (available for managed
model) and then forms an open circuit. The following illustration shows an application
example for wiring the fault alarm contacts.
Figure 4: Fault Alarm contacts
1
2 3 4 5 6
Note:
The wire gauge for the terminal block should be in the range between 12 ~ 24
AWG. Alarm relay circuit accepts up to 30V, max. 3A currents.
Figure 5: Alarm schematic
Industrial Switch
The cloesd circuit will poen when the
failure occurs.
Fault Alarm Contact 3 & 4
Insert the wires into the fault alarm contacts