beautypg.com

Interlogix NX-592E User Manual

Page 7

background image

NX-592E NetworX Cellular Module Installation Sheet

2. Enter 189#.

3. Press the STAY button to add a space at the beginning of

the zone name.

4. Press * to validate the space.

5. Press # and EXIT to exit Zone Name Programming Mode.

Wait one minute and then repeat the steps above. You should
see “ZMAX:xxx”, with no space at the beginning, and with xxx
being the highest zone number that the cellular module is

going to list in the equipment list. To change this number of

zones, do the following:

1. Press the STAY button to add a space at the beginning of

the zone name.

2.

Press * to move over the “:”

3.

Press “Chime” to remove the “:”

4. Press * to move over the digit you want to change.

5. Press the up or down arrow to change the digit.

6. Press * to validate the new digit.

7. Repeat steps 4, 5, and 6 with the other digits.

8. Press # and EXIT to exit Zone Name Programming Mode.

Within one minute, the cellular module will update its

equipment list according to the number of zones you specified.

This equipment list will be sent with the next phone test or

alarm.

Local Zones

Bit 8, segment 1 of the Zone Type Characteristic Select

locations determines whether the cellular module will report

alarms for this sensor type (See locations 111, 113, ..., 169).

If bit 8 is set, the panel and the module consider this sensor
type as “local” and will not report an alarm (The alarm will be
“reported” locally via the siren if so programmed).

Bypassed Zones

The cellular module will report bypass on a zone only when the
zone is in an “armed” state. The arming level of a zone is
determined by 4 bits of segment 1 of the Zone Type

Characteristic Select locations:

Bit 1: Fire zone

– Bypass is sent regardless of panel arming

state

Bit 2: 24 Hour zone

– Bypass is sent regardless of panel

arming state

Bit 7: Interior zone

– Bypass is sent only when panel is armed

away

Bit 8: Local zone

– Bypass is never sent how the updated list

of allowed reports. You can tell that the module updated the
fields by the fact that the leading space will have been
removed.

Troubleshooting/Testing

Check the cellular status LED 1 to see if it is flashing any

errors. See Table 5 on page 5 for descriptions of the errors

indicated.

Check cellular status LED 4 for signal strength (if it is toggling

on and off it is connected). If signal strength is less than 2, do a

walking signal strength test (see Module Location Guidelines

on page 2).

If touchpads/sirens are beeping even though the system is not

armed, press * 2 to display the trouble condition. Refer to

specific touchpad manual for more details.

Z-Wave devices

Required items for installation

NetworX panel (NX versions 4V2, 6V2, 8V2, 8E)

Alarm.com cellular Module with integrated Z-wave support

Z-Wave peripherals to be installed

Account creation and system setup

1. Create a new account on the Alarm.com Dealer Site (or

swap the module into an existing customer account). Add

the appropriate emPower services (Lights, Thermostats,

and/or Locks) on the service plan page. (Note that “Light

Automation” refers to X10 and is not compatible with

emPower.)

2. Install the Alarm.com Z-Wave-enabled cellular module and

gateway, connecting it to the NetworX panel.

3. Perform a cellular test at the panel to initiate

communication between the module and Alarm.com.

Make sure to install the Alarm.com module and gateway
outside the metal can. If it is inside the can, this will
negatively impact Z-Wave signal transmission.