beautypg.com

Interlogix NX-592E User Manual

Page 3

background image

NX-592E NetworX Cellular Module Installation Sheet

To wire the module:

1. Remove AC panel power and disconnect the backup

battery.

2. Wire the module to the panel bus and power terminals

(see Figure 3 below).

Figure 3: Wiring connections

POS COM DATA

KP POS KP COM KP DATA

Gateway

Panel

Case tamper switch (optional)

If the module is easily accessible, you can add case tamper

detection to activate an alarm or trouble (depending on panel

programming) when the cover is removed.

To install the tamper switch:

1. Slide the reed switch into the plastic holder on the module

back plate.

2. Connect a UL-Listed reed switch (with EOL resistor) to

any unused hardwired input on the panel.

3. Insert the magnet into the nibs on the top cover and press

the magnet clip down over the magnet until it clicks into
place into the cover.

Figure 4: Case tamper switch

Power up

You will need to power up the module and panel to start

communication between them.

To power up:

1. Verify that all wiring between the panel and module is

correct.

2. Connect the backup battery and restore AC power to the

panel.

3. Verify that radio status LED 1 is not flashing any errors

(see Cellular Status LEDs on page 4). Also, verify that
LED 4 is flashing a cellular signal level of two or higher.
Otherwise, relocate the module. If LED 1 and LED 4 are
not flashing, and LED 2 and LED 3 are flashing together,
the module is in Power Save mode and the battery needs
to be charged.

4. Perform a manual phone test by pressing *44 while the

system is disarmed (Make sure that panel’s Location 37,
Segment 2, Bit 7 is set).

Note: if Location 37, Segment 2, Bit 6 is set,

performing the phone test will trigger the local siren.

To avoid triggering the siren when performing the

phone test, make sure Bit 6 is OFF.

The panel will not show any indication that the phone test

signal has been sent. You can check the radio status LEDs L3

and L4: L4 should be blinking on for 2 seconds and off for 2

seconds. L3 will blink once briefly as soon as you press *44. If

the account is reporting to a Central Station, wait for a minute

and check with the Central Station to see if the phone test

signal was received correctly. The phone test is also used by

Alarm.com to set the module's parameters the first time the

module is powered up. It ensures that Alarm.com will receive

the sensors list and any other information required for proper

signaling.

Enrolling the module

The NetworX control panels automatically find and store in

memory the presence of all keypads, zone expanders, wireless

receivers, output modules, and any other device on the keypad

bus, allowing these devices to be supervised by the control

panel. To enroll the devices, enter Program Mode (refer to your

control panel documentation). When you exit Program Mode,

the control panel automatically enrolls the devices. This

process takes about 12 seconds. During this time, the Service

LED will illuminate and User codes will not be accepted. Once

a module is enrolled, if it is not detected by the control panel,

the Service LED will illuminate. When initially powering up, the

control panel automatically performs the device enrollment

process.

Programming using the keypad

The wireless gateway needs to know the address of at least

one of the LCD keypads. Some commands, such as getting

the zone names for display on the website, will not work if the

keypad address is not known. By default, the wireless gateway

assumes a keypad address of 192 (keypad 1, partition 1). If

your LCD keypad is programmed differently (press *94 +