The runtime calibration synchronizes the runtime estimate with the current
load and battery capacity. When a runtime calibration initiates, Calibration is
initiated event occurs. A runtime calibration will discharge the batteries. The
batteries will be completely discharged after the calibration. The batteries will
be recharged automatically following a calibration.

Note: Frequent calibration will shorten the life of batteries. We recommend one
or two calibrations per year.

PERFORM A RUNTIME CALIBRATION

1. Click the Start button; this will initiate a runtime calibration.
2. Click the Stop button; this will stop the runtime calibration.
3. Runtime Calibration will display the result after a calibration finishes or you
stop the calibration. The results will report as follows:

Estimated Runtime: The estimated runtime of the batteries.

Last Calibration Result: The result of the last runtime calibration.

o

Passed: Runtime calibration passed and the batteries are normal.

o

None: A runtime calibration has not been run.

o

Failed: The Battery Backup failed during the runtime calibration.

o

Cancelled: The runtime calibration was stopped...

Last Calibration Date: The date the last runtime calibration was performed.

Note: A calibration process causes the batteries to completely discharge. If a
utility power failure occurs during the calibration the Battery Backup will not
support the connected equipment.