beautypg.com

1005nc eng 6 7, Troubleshooting – Braeburn 1005NC User Manual

Page 4

background image

6

7

cont.

SYMPTOM

POTENTIAL SOLUTION

Thermostat turns

heating or cooling

system on too often or

not often enough.

Increase or decrease temperature differential setting as

appropriate to provide the desired performance level. See

Setting the Temperature Differential, section 4 of this manual.

Low battery indicator is

shown in thermostat

display.

Replace batteries immediately to maintain proper system

operation. See Low Battery Detection and Replacement, section

7 of this manual.

OFF is shown in

thermostat display and

heating or cooling

system will not start.

This indicates that the system is turned off at the thermostat.

Move the system selector switch to the

ON position.

Thermostat display

is blank.

It is possible that the batteries are drained and not providing

power for the thermostat to control the system. Replace

batteries immediately to maintain proper system operation. See

Low Battery Detection and Replacement, section 7 of this

manual. If you replace the batteries and the display does not

appear, call a professional service technician to verify

thermostat and system performance.

HI is shown in the

thermostat display

where the room

temperature is

normally displayed.

The temperature sensed by the thermostat is higher than the

90˚ F (32˚ C) upper limit of the thermostat’s display range. The

display will return to normal after the sensed temperature

lowers within the 45˚ to 90˚ F (7˚ to 32˚ C) display range.
This condition could occur from the system being turned off

during an exceptionally warm period or upon installation when

the thermostat has been stored for a long period of time in a

warm vehicle or location prior to being installed.

SYMPTOM

POTENTIAL SOLUTION

Thermostat will not

allow me to program a

setpoint temperature

higher than 90˚ F (32˚ C).

This is above the normal thermostat temperature setting range

of 45˚ to 90˚ F (7˚ to 32˚ C).

Thermostat will not allow

me to program a setpoint

temperature lower than

45˚ F (7˚ C).

This is below the normal thermostat temperature setting range

of 45˚ to 90˚ F (7˚ to 32˚ C).

Fan continues to run all

the time whether the

system is on or off.

Check that the fan control switch is in the

AUTO position.

This will allow the fan to run only when the heating or cooling

system is turned on and running.
Check thermostat wiring to make sure that the fan control

wiring is connected to the correct terminals on the wiring

terminal block. See Installation and Wiring Diagram sections

of this manual.

The room is too warm or

too cold.

See Review Set Temperature, section 5 of this manual to

verify the current set point and make any modifications that

are necessary.

LO is shown in the

thermostat display where

the room temperature is

normally displayed.

The temperature sensed by the thermostat is lower than the 45˚

F (7˚ C) lower limit of the thermostat’s display range. The display

will return to normal after the sensed temperature rises within

the 45˚ to 90˚ F (7˚ to 32˚ C) display range. If the temperature in

the controlled space seems to be normal, wait for the

thermostat to acclimate to the correct room temperature.
This condition could occur from the system being turned off

during a cold weather period or upon installation when the

thermostat has been stored for a long period of time in a cold

vehicle or location prior to being installed. The thermostat

should be allowed to warm up prior to installation to allow

proper heating control once installed.

Troubleshooting

8

cont.

Troubleshooting

8