BASO GM7000 Series Multi-function Gas Control Valve User Manual
Page 5
GM-7000 Series CE Approved Gas Control Valve Installation Instructions 5
Technical Specifications
Product
GM-7000 Series CE Approved Gas Control Valve
Types of Gas
Natural, Liquefied Petroleum (LP), and LP gas-air mixtures
Rated Inlet Pressure
North America:
Europe:
Australia:
1/2 psi
35 mbar
3.5 kPa
Maximum Working
Pressure (CE)
50 mbar
Maximum Differential
Pressure
20 mbar (2 kPa [8 in. W.C.])
Reverse Pressure Rating
50 mbar (5 kPa [20 in. W.C.]) Class B (EN 126 and 161); Class 2 (AS 4624 and AS 4629)
Regulator Classification
Class C (EN 126); Adjustable, Class 2, Grade 20 (AS 4624)
Regulator Setting
Factory set to customer’s specification
Direct-Acting Regulator
Pressure Range
Natural Gas:
LP Gas:
7.5 to 12.5 mbar (0.15 to 1.25 kPa [3 to 5 in. W.C.])
22.5 to 30 mbar (2.25 to 3 kPa [9 to 12 in. W.C.])
Permissible Ambient
(Surface) Temperature
0 to 70
°C (32 to 158°F )
Body Connections
1/2 NPT, 1/2 BSPP (Thread ISO 7-Rp) or 1/2 BSPT (Thread ISO 7-Rc) with Flange Connection Holes
(M4 x 0.7 mm pitch x 6 mm deep)
Valve Torsion Group
Group 2 (EN 126 and 161)
Pressure Taps
M5 x 0.8 Thread
Pilot Connection
1/4 in. cc Blank Plug
Materials
Body:
Diaphragms and Seals:
Die-Cast Aluminum
Nitrile Rubber
Dirt Strainer
0.9 mm (0.036 in.) mesh (CE only or upon request)
Operating Time Rating
100% Continuous
Valve Timings
Closing Time:
Opening Time:
Dead Time:
< 1 Second
< 1 Second
< 1 Second
Power Rating
10.5 VA per Coil
Electrical Rating
25 VAC, 50/60 Hz, 0.42A
Electrical Connection
2-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.)
3-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.) + 6.35 mm (1/4 in.) Earth Ground
Coil Insulation Class
Class F
Accessories
Conversion Kits
Natural gas to LP gas:
LP gas to Natural gas:
Regulated to non-regulated:
GM-70-CLP
GM-70-CNG
BG-70-CBP