beautypg.com

BASO GM7000 Series Multi-function Gas Control Valve User Manual

Page 5

background image

GM-7000 Series CE Approved Gas Control Valve Installation Instructions 5

Technical Specifications

Product

GM-7000 Series CE Approved Gas Control Valve

Types of Gas

Natural, Liquefied Petroleum (LP), and LP gas-air mixtures

Rated Inlet Pressure

North America:
Europe:
Australia:

1/2 psi
35 mbar
3.5 kPa

Maximum Working
Pressure (CE)

50 mbar

Maximum Differential
Pressure

20 mbar (2 kPa [8 in. W.C.])

Reverse Pressure Rating

50 mbar (5 kPa [20 in. W.C.]) Class B (EN 126 and 161); Class 2 (AS 4624 and AS 4629)

Regulator Classification

Class C (EN 126); Adjustable, Class 2, Grade 20 (AS 4624)

Regulator Setting

Factory set to customer’s specification

Direct-Acting Regulator
Pressure Range

Natural Gas:
LP Gas:

7.5 to 12.5 mbar (0.15 to 1.25 kPa [3 to 5 in. W.C.])
22.5 to 30 mbar (2.25 to 3 kPa [9 to 12 in. W.C.])

Permissible Ambient
(Surface) Temperature

0 to 70

°C (32 to 158°F )

Body Connections

1/2 NPT, 1/2 BSPP (Thread ISO 7-Rp) or 1/2 BSPT (Thread ISO 7-Rc) with Flange Connection Holes
(M4 x 0.7 mm pitch x 6 mm deep)

Valve Torsion Group

Group 2 (EN 126 and 161)

Pressure Taps

M5 x 0.8 Thread

Pilot Connection

1/4 in. cc Blank Plug

Materials

Body:
Diaphragms and Seals:

Die-Cast Aluminum
Nitrile Rubber

Dirt Strainer

0.9 mm (0.036 in.) mesh (CE only or upon request)

Operating Time Rating

100% Continuous

Valve Timings

Closing Time:
Opening Time:
Dead Time:

< 1 Second
< 1 Second
< 1 Second

Power Rating

10.5 VA per Coil

Electrical Rating

25 VAC, 50/60 Hz, 0.42A

Electrical Connection

2-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.)
3-Tab Solenoid Coil: 2 x 6.35 mm (1/4 in.) + 6.35 mm (1/4 in.) Earth Ground

Coil Insulation Class

Class F

Accessories

Conversion Kits

Natural gas to LP gas:
LP gas to Natural gas:
Regulated to non-regulated:

GM-70-CLP
GM-70-CNG
BG-70-CBP