BASO E Series AGA User Manual
BASO Hardware

Installation Instructions
Issue Date
June 12, 2014
©
2014 BASO Gas Products.
1
Part No. BASO-INS-ECA, Rev. A
www.baso.com
E Series CE/AGA Approved
Intermittent Pilot Ignition Control
Application
The E Series CE/AGA Approved Intermittent Pilot 
Ignition Control is a safety control designed for indirect 
burner ignition and supervision, for use with all gases 
and applicable to gas-fired appliances. 
The E Series is a microprocessor based ignition 
control. The microprocessor provides reliable software 
control of all timings and operates a diagnostic 
Light-Emitting Diode (LED). It provides ignition 
sequence, flame monitoring, and safety shutoff for 
boilers, furnaces and other gas-fired heating 
appliances. 
Installation
IMPORTANT:
Only qualified personnel should
install or service BASO Gas Products®. These 
instructions are a guide for such personnel. Carefully 
follow all instructions for the appliance. 
IMPORTANT:
Make all gas installations in
accordance with applicable local, national, and 
regional regulations. 
!
WARNING: Risk of Explosion or Fire.
Do not install the control in an area that is exposed 
to water (for example, dripping, spraying, rain). Do 
not use the control if it has been exposed to water. 
Exposure to water may cause malfunction and can 
lead to an explosion or fire and may result in severe 
personal injury or death. 
IMPORTANT:
This control is approved for use
with noise suppression (resistive) spark wires. If the 
application has copper wire, it must be replaced. 
Instructions for installing the pilot burner/igniter-sensor 
are typically provided by the appliance manufacturer. It 
is important to follow those instructions. If such 
information is not included, refer to the Mounting 
section. 
Mounting
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical 
connections to avoid electric shock. 
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the control. 
Failure to shut off the gas supply can result in the 
release of gas during installation or servicing, which 
can lead to an explosion or fire, and may result in 
severe personal injury or death. 
IMPORTANT:
Do not mount the control where
it can be exposed to direct infrared radiation from the 
main burner or to temperatures in excess of the 
maximum product temperature rating. 
Replacement Instructions
Mark wires to existing control. Disconnect the wires 
and remove the existing control. 
The control is not position sensitive. It may be 
mounted horizontally or vertically with two #6 sheet 
metal or machine screws.