beautypg.com

BASO GM7000 Series Multi-function Gas Control Valve User Manual

Gm-7000 series ce approved gas control valve

background image

Installation Instructions

GM-7000

Issue Date

November 9, 2012

© 2012 BASO Gas Products

1

Part No. BASO-INS-GM7000, Rev. F

www.baso.com

GM-7000 Series CE Approved Gas Control Valve

Installation

IMPORTANT: These instructions are intended as a
guide for qualified personnel installing or servicing
BASO Gas Products. Carefully follow all instructions
in this bulletin and all instructions on the appliance.
Limit repairs, adjustments, and servicing to the
operations listed in this bulletin or on the appliance.

!

WARNING: Risk of Fire or Explosion.

The system must meet all applicable local, national,
and regional regulations. Improper installation may
cause gas leaks, explosions, property damage, and
injuries.

!

WARNING: Risk of Fire or Explosion.

To prevent leakage of upstream gas, shut off the gas
supply at the main manual shutoff valve before
installing or servicing the GM-7000 valve. Failure to
shut off the gas supply can result in the release of
gas during installation or servicing, which can lead to
an explosion or fire, and may result in severe
personal injury or death.

Mounting

!

CAUTION: Risk of Equipment Damage.

To prevent damage to the valve when mounting to
pipework, do not use a wrench on any surface other
than the casting flats provided at the inlet and outlet
ends of the valve body.

To install the GM-7000 valve:

1.

Shut off power to the appliance.

2.

Shut off the gas at the main manual shutoff valve.

3.

Label each wire with the correct terminal
designation prior to disconnection.

4.

Compare the voltage on the valve with the power
source voltage to ensure the correct unit is being
installed.

5.

Mount the valve. The GM-7000 valve may be
mounted on a horizontal manifold with the
magnetic operators (solenoid coils) pointed up
(vertical) or in any position not exceeding 90

°

from the vertical (Figure 1). The valve may also
be mounted on a vertical manifold in any position
around its axis. Do not install the solenoid coils
upside down. Install vertically wherever possible.

6.

If you desire to measure the outlet pressure, use
the bottom cast pressure test fitting.

90° Maximum
from Vertical

90° Maximum

from Vertical

Limited Horizontal and Vertical

Vertical mounting may

be 360º around its axis
with the gas flow either

up or down, but always in
the direction of the arrow.

Figure 1: GM-7000 Mounting Positions

7.

Install the valve on the manifold; ensure the gas
flows through the valve body in the direction
indicated by the arrow on the body. If the valve is
installed with the gas flow in the opposite
direction of the arrow, leakage can occur.