H43 Series BASO®
Automatic Pilot Valve with Manual Shutoff
Applications
The H43 Series BASO valve is a combination A valve 
and automatic pilot valve. A manual valve handle with 
On, Off, and Pilot positions allows operation of the 
valve without a thermostat. Applications include room 
heaters, wall furnaces, and commercial cooking. 
Installation
IMPORTANT:
Only qualified personnel should
install or service BASO® Gas Products. These 
instructions are a guide for such personnel. Carefully 
follow all instructions in this document and all 
instructions for the appliance. 
IMPORTANT:
Make all gas installations in
accordance with applicable local, national, and 
regional regulations. 
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical 
connections to avoid electric shock. 
Note: In applications that do not require electrical 
power, disregard the previous caution. 
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the H43. Failure 
to shut off the gas supply can result in the release of 
gas during installation or servicing, which can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 
IMPORTANT:
Verify that the valve is installed
only in applications where the specified maximum 
ambient (surface) temperature and maximum 
operating pressure do not exceed the limits in the 
Technical Specifications section. 
To install the H43 valve:
1.
Shut off power to the appliance (if applicable).
2.
Shut off the gas at the main manual shutoff valve.
3.
Ensure that the gas flows through the valve body 
in the direction indicated by the arrow on the 
valve body. If the valve is install with the gas flow 
in the opposite direction of the arrow, leakage 
can occur. 
IMPORTANT:
Do not use a wrench on any
surface other than the casting flats provided at the 
inlet and outlet ends of the valve body. The H43 may 
be damaged in the mounting process if a wrench is 
used on any other surface. Using a wrench 
incorrectly may void the warranty. 
4.
Mount the valve to the pipework. Mount the H43 
valve in any convenient position with the reset 
button and manual valve handle accessible. Use 
an approved pipe joint sealing compound on the 
male threads before assembly. Remove excess 
compound after mounting the valve to the 
pipework. Threads of the pipe and nipples must 
be smooth and free of tears and burrs. Steam 
clean all piping to remove foreign substances 
such as cutting oil or thread chips. A sediment 
trap needs to be installed in accordance with the 
National Fuel Gas Code NFPA 54 (Figure 1). 