G92 Series BASOTROL® Automatic Pilot Gas Valve
Installation
IMPORTANT:
Only qualified personnel should
install or service BASO® Gas Products. These 
instructions are a guide for such personnel. Carefully 
follow all instructions in this document and all 
instructions for the appliance. 
IMPORTANT:
Make all gas installations in
accordance with applicable local, national, and 
regional regulations. 
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the G92. Failure 
to shut off the gas supply can result in the release of 
gas during installation or servicing, which can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 
!
CAUTION: Risk of Electrical Shock.
Disconnect power supply before making electrical 
connections to avoid electrical shock. 
IMPORTANT:
Verify that the valve is installed
only in applications where the specified maximum 
ambient (surface) temperature and maximum 
operating pressures will not exceed the limits in the 
Technical Specifications section. 
To install the G92 valve:
1. Shut off the gas at the main manual shutoff valve. 
2. Compare the voltage on the valve with the power 
source voltage to ensure the correct unit is being 
installed. For valves with 25 volt coils, use a 
National Electrical Code (NEC) Class 2 
transformer. 
Note: The transformer must be mounted to a 
grounded metal enclosure. 
3. Ensure that the gas flows through the valve body 
in the direction indicated by the arrow on the valve 
body when installing the valve on the manifold. If 
the valve is installed with the gas flow in the 
opposite direction of the arrow, leakage can occur. 
IMPORTANT:
Do not use a wrench on any
surface other than the casting flats provided at the 
inlet and outlet ends of the valve body. The G92 may 
be damaged in the mounting process if a wrench is 
used on any other surface. Using a wrench 
incorrectly may void the warranty. 
 
4. Mount the G92 valve on a horizontal manifold with 
the magnetic operator point up (vertical) or in a 
position not exceeding 90
° from vertical. The valve
may also be mounted on a vertical manifold in any 
position around its axis (see Figure 1). 
Vertical mounting may be 360º
around its axis with the gas flow
either up or down, but always in
the direction of the arrow.
Horizontal mounting limited
to 90º from upright.
90º
90º
Figure 1: G92 Mounting Positions