BASO G93 Series Combination Automatic Gas Valve User Manual
BASO Hardware

Installation Instructions
Issue Date
September 17, 2008
©
2008 BASO Gas Products
1
Part No. BASO-INS-G93 Rev. A
www.baso.com
G93 Series BASOTROL® Combination
Automatic Gas Valve
Application
The G93 valves are suitable for use with natural gas, 
Liquefied Petroleum (LP) gas, or LP gas-air mixtures. 
Typical applications include central heating units, unit 
heaters, commercial clothes dryers, and similar 
applications. 
Installation
IMPORTANT:
Only qualified personnel should
install or service BASO Gas Products products. 
These instructions are a guide for such personnel. 
Carefully follow all instructions in this document and 
all instructions for the appliance. 
IMPORTANT:
Make all gas installations in
accordance with applicable local, national, and 
regional regulations. 
!
CAUTION: Risk of Electric Shock.
Disconnect power supply before making electrical 
connections to avoid electric shock. 
!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the G93. Failure 
to shut off the gas supply can result in the release of 
gas during installation or servicing, which can lead to 
an explosion or fire, and may result in severe 
personal injury or death. 
!
WARNING: Risk of Explosion, Fire, or
Electric Shock. Label all wires before they are 
disconnected when replacing or servicing the G93. 
Wiring errors can cause improper or dangerous 
operation and may result in an explosion, fire, or 
electric shock leading to severe personal injury or 
death. 
IMPORTANT:
Verify that the valve is installed
only in applications where the specified maximum 
ambient (surface) temperature and maximum 
operating pressures will not exceed the limits in the 
Technical Specifications section. 
To install the G93 valve:
1. Shut off power to the appliance.
2. Shut off the gas at the main manual shutoff valve.
3. Label each wire with the correct terminal
designation prior to disconnection.
4. Compare the voltage on the valve with the power
source voltage to ensure the correct unit is being 
installed. For valves with 25-volt coils, use a 
National Electrical Code (NEC), Class 2 
transformer. 
Note: The transformer must be mounted to a
grounded metal enclosure.
5. Ensure that the gas flows through the valve body
in the direction indicated by the arrow on the valve 
body. If the valve is installed with the gas flow in 
the opposite direction of the arrow, leakage can 
occur. 
IMPORTANT:
Do not use a wrench on any
surface other than the casting flats provided at the 
inlet and outlet ends of the valve body. The G93 may 
be damaged in the mounting process if a wrench is 
used on any other surface. Using a wrench 
incorrectly may void the warranty. 