E Series CE/AGA Approved Intermittent Pilot Ignition Control Installation Instructions 5
Troubleshooting
If the system does not function properly, determine the
cause using the procedures in this section.
Before proceeding with troubleshooting the system, check
the following.
Preliminary Checks
Are you using resistive wire between the module
spark (11) and the pilot connection?
Are all mechanical and electrical connections tight?
Is the system wired and grounded correctly?
Is gas inlet pressure per manufacturer’s
specifications?
Is the thermostat calling for heat?
Is the system powered?
Table 1: LED Error Indications
LED Indications During Normal Operation
Orange once a second
Waiting Time (Prepurge)
Red rapid flashing
Safety Time Spark On (Trial for Ignition)
Steady green
Running Position Flame On (Run)
Orange once every 5 seconds
Inter-Waiting Time Between Cycles (Retry)
Orange once a second
Flame Loss Waiting Time (Inter-Purge)
LED Error Indications
Red Green
Error
1
0
Flame did not light in safety time (Trial for Ignition)
1
1
Flame sense circuit stuck on
1 2
Internal
fault
1
3
Line frequency or micro clock error
2
1
Pilot valve fault
2
2
Pilot valve relay contact fault
2
3
Main relay fault
2
4
Main valve relay contact fault
Note: More than 2 red blinks indicate micro-memory or software fault.