Technical specification – BASO BGQ15HAA-1 User Manual
Page 16
16 BGQ15HAA-1 Retrofit Spark Ignition System Installation Instructions
Technical Specification
Product
BG1600M10EK-1AA Intermittent Pilot Ignition Control
Ignition Type
Indirect
Ignition Source
High voltage spark, capacitive discharge
High Voltage Cable
Maximum Length
48 in. (1,220 mm) (Resistive wire recommended, rated for at least 15kV.)
Flame Sense Cable
Maximum Length
48 in. (1,220 mm)
Flame Detection Means
Flame Rectification
Flame Detection Type
Remote
Minimum Flame Current
0.15 microamperes
Flame Failure Response
Time
2 seconds maximum
Maximum Spark Gap
0.2 in. (5.1 mm)
Number of Trials Before
100% Shutoff
One
Trial-for-Ignition Time
Infinite
Prepurge Time
None
Inter-Purge Time
5 seconds
Automatic Recycle Delay
Period
None
Power Requirements
Control:
Operation Current:
24 VAC (+/- 20%), 50/60 Hz
0.2 A nominal + valves
Contact Rating
Main Valve:
Pilot Valve:
2 A maximum
1 A maximum
Wiring Connections
1/4 in. (6.35 mm) male spade
Maximum Firing Rate
400,000 Btu/hr (117 kW)
Ambient Operating and
Storage Temperature
-40 to 170
°F (-40 to 77°C)
Humidity
95% RH noncondensing
Type of Gas
Natural, Liquefied Petroleum (LP), Manufactured, Mixed or LP Gas-Air Mixture
Packaging
Bulk pack supplied to original equipment manufacturer (25 per box)
Individual pack (1 per box)
Individual overpack (20 per box)
Pack Weight
Bulk pack 14 lb (6.36 kg)
Individual pack 1 lb (.454 kg)
Individual overpack 18 lb (8.17 kg)
Agency Listing
CSA Certificate Number 246569-2161442
Specifications Standards
ANSI Standard Z21.20
CAN/CSA-C22.2 No. 199
The performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is
performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and
may void the warranty. If the product is exposed to water (dripping, spraying, rain, etc.) or other harsh environments, it must be protected. The
original equipment manufacturer or end user is responsible for the correct application of BASO products. For questionable applications, please
consult BASO Gas Products LLC. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from
misapplication or misuse of its products.