BGH2UNCTRLHT-01 Universal Hot Surface Ignition Control Installation Instructions 3
Table 1: BGH2UNCNTRLHT-01 Universal Cross Reference
Switch
Positions
ON
Switch
Positions
OFF
White-Rodgers Robershaw Honeywell Fenwal
2 1,3,4,5
50E47-130 to 139
50E47-330 t 339
―
―
―
2,5 1,3,4
50E47-120 to 129
50E47-320 to 329
―
―
―
2,4 1,3,5
50F47-130 to 139
50F47-330 to 339
―
―
―
2,4,5 1,3
50F47-120 to 129
50F47-320 to 329
―
―
05-356225-153(d,g)
05-356225-154(d,g)
05-356225-155(d,g)
2,3 1,4,5
50E47-110 to 119
50E47-310 to 319
50F47-110 to 119
50F47-310 to 319
―
―
―
2,3,5 1,4
50E47-101 to 109
50E47-301 to 309
50F47-101 to 109
50F47-301 to 309
HS780-17NL-108A(a)
―
05-356225-053(c,d)
05-356225-054(c,d)
05-356225-055(c,d)
2,3,4 1,5
―
―
8910U
S890D1006(a,e)
S890C1007(a,e)
―
2,3,4,5 1
― HS780-34NL-108A(a)
S89D1002(a)
S89C1004(a)
S89J1008(a)
S89C1012(a)
―
1 2,3,4,5
50E47-50 to 59
50E47-250 to 259
―
―
―
Note: For timing parameters see Table 2.
(a)
The BGH2UNCNTRLHT-01 Universal and the referenced control ignition trial times are different; however, the
ignition trial time is within the design tolerance of the referenced control.
(b)
The BGH2UNCNTRLHT-01 Universal between trial purge time is longer than that of the referenced control.
(c)
The BGH2UNCNTRLHT-01 Universal between trial purge and igniter warmup times is longer than those of the
referenced control.
(d)
The BGH2UNCNTRLHT-01 Universal ignition trial time is shorter than that of the referenced control. Be sure
to observe appliance operation to assure reliable performance.
(e)
The BGH2UNCNTRLHT-01 Universal pre-purge time is longer than that of the referenced control
(f)
The BGH2UNCNTRLHT-01 Universal pre-purge and between trial purge times are longer than those of the
referenced control.
(g)
The BGH2UNCNTRLHT-01 Universal pre-purge, between trial purge, and igniter warmup times are longer
than those of the referenced control.