BASO BG1600M 2014 User Manual
Page 3
BG1600M Intermittent Pilot Ignition Control Installation Instructions 3
MV
MV/PV
(COM)
PV
GN
D
B
URNE
R
GND
24V
TH
SENSE
INT
E
RNA
L
SPARK
Thermostat
High
Temp
Limit
Pilot
Burner/ignitor
Combination
Gas Valve
24VAC
Class 2
Transformer
1
2
3
4
5
6
7
8
10
9
L1 (Hot)
L2 (Neu)
1
2
3
4
1
2
Power Supply. Provides disconnect means and overload protection as required.
Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)
4
3
Alternate location for limit controller.
Controls in 24V circuit must not be in ground leg to transformer.
Chassis or Frame
Ground
5
Sensor rod must be 3/8” (9.53 mm) to 1/2” (12.7 mm) of the sensor tip should
be in the flame for proper sensing signal.
5
Figure 1: Wiring for 1 Rod Flame Sense without Vent Damper Jumper Plug
MV
MV/PV
(COM)
PV
GN
D
B
URNE
R
GND
24V
TH
SENSE
INT
E
RNA
L
SPARK
Thermostat
High
Temp
Limit
Pilot
Burner/ignitor
Combination
Gas Valve
24VAC
Class 2
Transformer
1
2
3
4
5
6
7
8
10
9
L1 (Hot)
L2 (Neu)
1
2
3
4
1
2
Power Supply. Provides disconnect means and overload protection as required.
Maximum cable length 48 inches (1,220 mm). (Resistive wire recommended.)
4
3
Alternate location for limit controller.
Controls in 24V circuit must not be in ground leg to transformer.
Chassis or Frame
Ground
5
Sensor rod must be 3/8” (9.53 mm) to 1/2” (12.7 mm) of the sensor tip should
be in the flame for proper sensing signal.
Use jumper
plug supplied
with control.
5
Figure 2: Wiring for 1 Rod Flame Sense with Vent Damper Jumper Plug