BG1100M Direct Spark Ignition Control Installation Instructions 15
Technical Specification
Product
BG1100M Direct Spark Ignition Control
Ignition Type
Direct
Ignition Source
High voltage spark, capacitive discharge
High Voltage Cable
Maximum Length
48 in. (1,220 mm) (Resistive wire only, rated for at least 15kV.)
Flame Sense Cable
Maximum Length
48 in. (1,220 mm)
Flame Detection Means
Flame Rectification
Flame Detection Type
Local or Remote
Minimum Flame Current
0.15 microamperes
Flame Failure Response
Time
2 second maximum
Maximum Spark Gap
0.2 in. (5.1 mm)
Number of Trials Before
100% Shutoff
One or Three
Trial-for-Ignition Time
4, 8, 10 or 20 seconds
Prepurge Time
0 (none), 15 or 30 seconds
Inter-Purge Time
0 (none) or 30 seconds
Retry (Recycle) Delay
Period
0 minutes (none)
5 minutes
Power Requirements
Control:
Operation Current:
24 VAC (+/- 20%), 50/60 Hz
0.2 A nominal + valves
Contact Rating
Valve:
2 A maximum
Wiring Connections
1/4 in. (6.35 mm) male spade
Maximum Firing Rate
400,000 Btu/hr (117 kW)
Ambient Operating and
Storage Temperature
-40 to 170
°F (-40 to 77°C)
Humidity
95% RH noncondensing
Type of Gas
Natural, Liquefied Petroleum (LP), Manufactured, Mixed or LP Gas-Air Mixture
Packaging
Bulk pack supplied to original equipment manufacturer (individual pack optional)
Bulk Pack Quantity
25
Pack Weight
14 lb (6.36 kg)
Agency Listing
CSA Certificate Number 246569-2161442
Specifications Standards
ANSI Standard Z21.20
CAN/CSA-C22.2 No. 199
The performance specifications are nominal and conform to acceptable industry standards. All agency
certification of BASO products is performed under dry and controlled indoor environmental conditions. Use of
BASO products beyond these conditions is not recommended and may void the warranty. If the product is
exposed to water (dripping, spraying, rain, etc.) or other harsh environments, it must be protected. The original
equipment manufacturer or end user is responsible for the correct application of BASO products. For questionable
applications, please consult BASO Gas Products LLC. BASO Gas Products LLC shall not be liable for damages
or product malfunctions resulting from misapplication or misuse of its products.
1007 South 12th Street
PO Box 170
Watertown, WI 53094
Published in U.S.A.
1-877-227-6427
www.baso.com