VA-115 INSTRUCTIONS – ELECTRONIC CONTROL VALVE, CXT-E

8-14

Figure 8-6. Linkage Assemblies



If necessary, the Linkage Assembly is removed and replaced as follows:

CM57. Remove the Actuator using steps CM45 through CM48 in the previous paragraph titled

ACTUATOR REPLACEMENT.

CM58. Next, refer to Figure 8-1 (1” to 2” Valves or 8-2 (2 ½” to 4” Valves) to locate item numbers shown

in parentheses in the following steps.

CM59. Loosen the Hex Nuts (17) under the Indicator Plate (Figure 8-1 or 8-2) approximately a half turn

clockwise. To simplify Linkage Assembly replacement, DO NOT remove the Hex Nuts. This will
simplify adjustment of the Linkage during reassembly.

CM60. Remove the Shaft Pin (Figure 8-1 or 8-2) securing the Linkage Shaft to the Linkage Adapter.

CM61. Remove the Linkage Adapter (Figure 8-1, 8-2) from the Valve Shaft (16) by rotating it counter-

clockwise. Also, remove the Indicator Plate.