beautypg.com

AERCO Electronic Control Valve User Manual

Page 22

background image

VA-115 INSTRUCTIONS – ELECTRONIC CONTROL VALVE, CXT-E

7-2

TABLE 7-1. TROUBLESHOOTING – CONTROL VALVE CXT-E

NO.

FAULT INDICATION

PROBABLE CAUSE

CORRECTIVE ACTION

T1

System not operating.

Control Valve is closed
and outlet water temp. is
far below setpoint.

1. No power supplied to

Control Valve



2. Control signal not

being supplied from
Temp. Controller.

1. Disconnect Valve Actuator plug and

verify that 24 VDC power is present at
pin 2 of Actuator cable. Restore power
if necessary. If System includes an
over-temp limiting device, ensure that it
has not tripped.

2. Verify presence of 4 - 20 mA control

signal at pin 3 of Actuator cable. If
control signal is not present,
troubleshoot Temp. Controller.

T2

System over-heats by
more than 10°F above the
desired setpoint.
Outlet temp is below Over-
Temp limit setting

CAUTION

Over-tightening the Pack-
ing Nut may trap the Valve
Stem and slow or stop
Valve motion.

1. Control Valve not fully

closed.



2. Temp. Controller not

set properly or
defective.


3. Valve Actuator not

properly secured to
Linkage Assembly.

4. Foreign matter in

Valve Seat.

1. Check the 4 – 20 mA control signal

being supplied to Actuator. If signal is
greater than 4 mA when heater outlet
temperature is 10°F (or more) above
the desired setpoint, proceed to next
item in list.

2. Check the current setting of Temp.

Controller providing the 4 – 20 mA
control signal to the Valve Actuator.
Readjust if necessary. If adjustment
does not clear fault, troubleshoot the
Controller.

3. Check Actuator U-bolt securing it to

Linkage Assembly. Tighten if needed
and readjust the CXT-E Control Valve
per Section 3.

4. If Valve still does not close after

checking the above items, disassemble
the Valve and clean the Seat per steps
CM18 – CM28 in Section 8. Readjust
the CXT-E Control Valve per Section 3.

T3 System

outlet

water

temperature is below
desired setpoint

CAUTION

Over-tightening the Pack-
ing Nut may trap the
Valve Stem and slow or
stop Valve motion.

1. Temp. Controller not

properly set.

2. Control Valve not

opening properly.











1. Check the current setting of the Temp.

Controller. If the setting is below the
desired setpoint, readjust as necessary.

2. Check as follows:

a. Ensure Actuator is secured to

Linkage Assembly. Tighten if needed
and readjust the CXT-E Control
Valve per Section 3.

b. Verify that 24 VDC power and 4 – 20

mA control signal are present at
Actuator pins 2 and 3 respectively.

c. To ensure Valve is not binding,

check Seal Retainer per steps CM1-
CM10 of Section 8 Corrective
Maintenance. Replace items as
necessary.