beautypg.com

AERCO MXG-461 Series Control Valve - Manufactured by Siemens User Manual

Page 6

background image

6/14

Siemens

Modulating control valves with magnetic actuators, PN16

CA1N4455en

Building Technologies

15.12.2009

The two-color LED display indicating operating status can be viewed by opening the
cover of the electronics module.

LED

Indication

Function

Remarks, troubleshooting

Green Lit

Control mode

Automatic operation; everything o.k.

Flashing

Calibration

In manual control

Wait until calibration is finished
(green or red LED will be lit)
Hand wheel in MANUAL or OFF position

Red Lit

Calibration error
Internal error

Recalibrate (operate button in opening 1x)
Replace electronics module

Flashing

Mains fault

Check mains network (outside the frequency or
voltage range)

Both

Dark

No power supply
Electronics faulty

Check mains network, check wiring
Replace electronics module

As a general rule, the LED can assume only the states shown above (continuously red
or green, flashing red or green, or off).

Sizing

Δp

V100

= differential pressure across the fully open valve and the valve’s control path A

→ AB by a

volume flow V

100

V

100

= volume flow through the fully open valve (H

100

)

Δp

max

= max. permissible differential pressure across the valve’s control path for the entire actuating

range of the motorized valve

100 kPa = 1 bar

≈ 10 mWC

1 m

3

/h = 0.278 l/s water at 20 °C

When sizing valves for media other than water, note that the medium properties

• specific

heat

• density
• kinematic

viscosity

differ from water. All variables depend on temperature. The design temperature is the
lowest medium temperature in the valve.

Indication of
operating state

Flow chart

Note for media other
than water