TROUBLESHOOTING

16. Shut down VFD power.

17. Turn On VFD power.

18. Set Pr. 59 to 1

19. Recalibrate the boiler using the combustion calibration procedures in Chapter 4.




Table 8-5. VFD Faults

NOTE

Check parameters 55, 56, 57, & 58 for the last 4 Trips.

VFD Fault

Possible Cause

U U

Low AC supply voltage

OU

High AC supply voltage

O.ht2

High ambient temperature

CL1

Analog input loss
(4-20 mA Air/Fuel Valve position signal)

EEF

Possible loss of parameters values

C.dAt

Empty SmartStick has been read

C.Err

Bad connection or faulty SmartStick

C.Acc

Bad connection or faulty SmartStick