beautypg.com

Installation, Danger – AERCO BMK 2.0 LN Natural Gas 2008 User Manual

Page 16

background image

INSTALLATION

2-6

In addition to the terminal strips shown in Figure
2-9, the I/O Box also contains a pre-wired
temperature transmitter which receives inlet air
temperature sensor readings and transmits this
signal to the variable frequency drive (VFD)
contained in the Boiler. The VFD utilizes this
input signal to adjust the rotation speed of the
blower.

Brief descriptions of each mode of operation,
and their wiring requirements, are provided in
the following paragraphs. Additional information
concerning field wiring is provided in paragraphs
2.10.1 through 2.10.10. Refer to Chapter 5 for
detailed information on the available modes of
operation.

2.9.1 Constant Setpoint Mode

The Constant Setpoint Mode is used when it is
desired to have a fixed setpoint that does not
deviate. No wiring connections, other than AC
electrical power connections, are required for
this mode. However, if desired, fault monitoring
or enable/disable interlock wiring can be utilized
(see paragraphs 2.10.9.1 and 2.10.10).

Figure 2-9.

Input/Output (I/O) Box Location

mA OUT

RS-485
COMM.

+

-

+
-

ANALOG IN

SENSOR COMMON

OUTDOOR SENSOR IN

REMOTE INTL'K IN

B.M.S. (PWM) IN

SHIELD

+
-

+
-

AUX SENSOR IN

NOT USED

EXHAUST SWITCH IN

DELAYED INTL'K IN

FAULT RELAY
120 VAC, 5A, RES

AUX RELAY
120 VAC, 5A, RES

G

RELAY CONTACTS:
120 VAC, 30 VDC
5 AMPS RESISTIVE

DANGER

120 VAC USED

IN THIS BOX

NOT USED

NOT USED

NC
COM
NO

NC
COM
NO

NOT USED

Figure 2-10. I/O Box Terminal Strip