1. FOREWARD

The AERCO Boiler Valve Controller (BVC) is designed for variable flow heating systems. The

BVC can be configured to control each motor operated valve (MOV) independently to minimize

the system flow requirements in a multiple boiler plant. Using the BVC in your system design will

save energy, help eliminate over-temperature faults and improve the life and reliability of your

AERCO Boilers.

For example, a four BMK2.0LN installation typically requires 4 x 25 = 100 GPM minimum

system flow for stable operation. The same installation with MOVs and the AERCO Boiler Valve

Controller will allow 25 GPM minimum system flow since the system is reduced to single boiler

operation and flow is stopped on the other three boilers. As boilers are started up and turned off

based on system demand the valve controller can be configured to open and close the valves to

meet the heating demand and maintain stable temperature control without the risk of over-

temperature faults. When system demand is satisfied and all the boilers are off, the Boiler Valve

Controller opens all the MOVs, preventing system pump dead head conditions.

The valve controller has a simple, easy to use menu structure. The position of any MOV can be

selected using the BVC “Valves” Screen. However if a boiler is firing, the BVC will not allow you

to change the valve to the “CLOSED” position in order to avoid exceeding safe operating

temperature at the boiler. The factory default delay time setting is 2 minutes. The controller may

be programmed from one to thirty minutes in one-minute increments.