2 scenario 2, Gf-126 boiler valve controller (bvc) – AERCO Boiler Valve Controller (BVC) User Manual

Page 33

background image

GF-126

Boiler Valve Controller (BVC)

OMM-0051_0D

User Manual

VD2: 01/20/13 Page 33 of 38

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288





















Figure 13 - Valve Control Scenario 1


5.4.2 Scenario 2

In this scenario depicted in Figure 14, none of the boilers are firing and all of the valves are

open. All MOVs are placed in the “OPEN” position. A boiler MOV can be manually closed by

selecting the “Valves” touch screen.
The scenario sequence is described as follows (See Figure 11).

1.

From the Main screen press the “VALVES” touch screen button (see Figure 11, Screen1).

2.

This brings the user to Screen 2 where either the “VALVES 1-2” or “VALVES 3-4” screens

may be selected by pressing their corresponding touch screen button. The user is now

brought to either the “VALVE 1-2” screen (Screen 3) or the “VALVE 1-2” screen (Screen 4).

If the “BACK” touch screen button was pressed instead, the user would have navigated back

to the Main screen.

Can’t close while

boiler is firing

Press to open

Screen 3

Screen 1

Screen 4

Screen 2