Boiler valve controller (bvc), Gf-126 – AERCO Boiler Valve Controller (BVC) User Manual

Page 14

background image

Boiler Valve Controller (BVC)

GF-126

User Manual

OMM-0051_0D

Page 14 of 38 VD2: 01/20/13

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

NOTE

The I/O Terminal Strips for the KC and Benchmark Boiler series are

identical.

4.4.3

22B

Connecting the Required Electrical Components (4 Boiler Version)

1. Refer to Figure 6 illustrating the Boiler I/O Box and locate the Auxiliary (AUX) Relay

terminals on the lower right terminal strip.

2. Connect the NO (Normally Opened) and COM (Common) terminals of the AUX Relay (on

the Boiler I/O Box) to the appropriate terminals of the Boiler Valve Controller as shown in

Figures 6 and 8. Tables summarizing the connection terminals on the BVC follow.

Table 1 - BVC Connection Terminals from Boiler I/O Box AUX Relay (4 Boiler System,

Models 64064, 64095, 64097)

4 Boiler System

Terminal Block

Connections

Boiler I/O Box

NO Terminal

Boiler I/O Box

COM Terminal

Boiler #1 Relay

1

13

Boiler #2 Relay

2

14

Boiler #3 Relay

3

15

Boiler #4 Relay

4

16

3. Next, refer to Figure 8 and connect the CLOSE/OPEN/COMMON terminals in each MOV

to the appropriate terminals in the BVC. Tables summarizing the connection terminals on

the BVC follows:

Table 2 - Connection Terminals on the BVC from MOV 4 Boiler System, Models 64064,

6409, 64097)

4 Boiler System BVC

Terminal Connections

MOV

Close

Terminal

MOV

Open

Terminal

MOV

Common

Terminal

MOV

Hot

Terminal

MOV #1 (V-1)

17

5

9

21

MOV #2 (V-2)

18

6

10

22

MOV #3 (V-3)

19

7

11

23

MOV #4 (V-4)

20

8

12

24

4. Finally, refer to Figure 8 and connect the Delayed Interlock terminals (DELAYED INTL’K

IN) in the Boiler I/O Box (Figure 6) to the Open End Switch terminals on the

corresponding MOV.