OPERATION

29

3.4

15B

MANUAL VALVE CONTROL SCENARIOS

Two common scenarios are presented in the Scenario 1 and Scenario 2 subsections that follow.

NOTE

The MOV of a firing boiler cannot be manually overridden to the “CLOSED” position.

3.4.1

Scenario 1

In this scenario, depicted in Figure 14 below, Boilers #1 and #2 are firing and the corresponding

MOVs #1 and #2 are automatically opened. A boiler MOV can always be manually opened by

utilizing the “Valves” screen.

The scenario sequence is described as follows (See Figure 14).

1.

From the Main screen press the “VALVES” touch screen button (Figure 14 – Screen1).

2.

This action displays Screen 2 where either the “VALVES 1-2” or “VALVES 3-4” screens may

be selected by pressing their corresponding area of the touch screen. The user is now

brought to either the “VALVE 1-2” screen (Screen 3) or the “VALVES 3-4” screen (Screen

4). If the “BACK” touch screen button was pressed instead, the user would have navigated

back to the Main screen.

3.

On the “VALVES 1-2” screen (Screen 3) the user cannot effect any change because those

boilers are assumed to be firing in this particular scenario. The two valves (Valve # 1 and

Valve # 2) are already in the “OPEN” position and cannot be manually closed while their

respective boilers are firing. Pressing the “BACK” touch screen button returns the user to

Screen 2 where the user may either choose to select the “VALVES 3-4” screen (Screen 4)

or simply press the “BACK” touch screen button and return to the Main screen.

4.

If the user went to screen 4 instead, either Valve #3 or Valve #4 may be manually opened

since their respective boilers are not currently firing.

5.

If the user navigated back to the Main screen the user may now choose to press the

“TIMER” touch screen button and set the boiler valve delay time in effect before the valves

can be closed.