Pin settings, Input/output circuit, Input circuit – KEYENCE CV-X200 Series User Manual
Page 6: Output circuit
6
OUTPUT connector
• Socket block:
MC1.5/9-ST-3.5BK
(Phoenix Contact)
• Suitable wiring
AWG 16 - 28
• Terminal block screw torque
0.25 Nm or less
INPUT connector
• Socket block:
MC1.5/6-ST-3.5BK
(Phoenix Contact)
• Suitable wiring
AWG 16 - 28
• Terminal block screw torque
0.25 Nm or less
Pin Settings
OUTPUT connector
INPUT connector
Input Circuit
Input circuit diagram
Circuit A (F_IN0 to 3 only, EV compatible)
• Max. imposed voltage: 26.4 V
• ON voltage: 10.8 V or greater
• ON current: 3 mA or greater
• OFF voltage: 5 V or less
• OFF current: 1 mA or less
Circuit B (other inputs)
• Max. imposed voltage: 26.4 V
• ON voltage: 10.8 V or greater
• ON current: 2 mA or greater
• OFF voltage: 3 V or less
• OFF current: 0.3 mA or less
Output Circuit
Output circuit diagram (NPN output type)
Circuit C (F_OUT0 to 3 only)
• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or
less
• Residual voltage:
1.4 V or less (50 mA)
1.0 V or less (20 mA)
Circuit D (Other outputs)
• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or
less
• Residual voltage:
1.4 V or less (50 mA)
1.0 V or less (20 mA)
Output circuit diagram (PNP output type, controllers with a "P" at
the end of the part number)
Circuit C (F_OUT0 to 3 only)
• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or
less
• Residual voltage:
1.4 V or less (50 mA)
1.0 V or less (20 mA)
Circuit D (Other outputs)
• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or
less
• Residual voltage:
1.4 V or less (50 mA)
1.0 V or less (20 mA)
*1: It is the default assigned value on the terminal where the
signal assignment can be changed. These assignments may
vary if the Global settings have been changed.
*2: For more details about the signal description, see the
"
CV-X
Series User's Manual
"
.
No.
Terminal
name
Signal
Terminal block
display at time
of shipment
Signal
description
*2
Circuit
diagram
1
OUT22
STO
STO
Output timing indicator
D
2
OUT23
OR
OR
Total status output
D
3
F_OUT2
ERROR
*1
ERR
Error output
*1
C
4
F_OUT3
RUN
*1
RUN
Run mode output
*1
C
5
COMOUT1
–
COMOUT
Common for terminal
block outputs
–
6
F_OUT0
FLASH 1
FLS1
Strobe light output for
trigger 1
C
7
F_OUT1
FLASH 2
FLS2
Strobe light output for
trigger 2
C
8
COMOUT_
F+
–
(COMF+)
+ common for terminal
output
–
9
COMOUT_
F-
–
(COMF-)
- common for terminal
output
–
• Power source 0V, COMOUT1, COMOUT_F+, and
COMOUT_F- are all isolated.
• COMOUT1 is the common terminal for output for OUTPUT
connectors 1 to 2.
• COMOUT_F+ and COMOUT_F- are the common terminals for
OUTPUT connectors 3 to 4 and 6 to 7.
No.
Terminal
name
Signal
Terminal block
display at time
of shipment
Signal
description
*2
Circuit
diagram
1
COMIN1
–
COMIN
Common for terminal
block inputs
–
2
IN15
PLC
*1
PLC
Command read request
from PLC
*1
B
3
F_IN0
TRG1
TRG1
Trigger 1 input
A
4
F_IN1
TRG2
TRG2
Trigger 2 input
A
5
F_IN2
TEST
*1
TEST
Trial run input
*1
A
6
F_IN3
EXT
*1
EXT
Disable trigger input
*1
A
• Power source 0V and COMIN1 are all isolated.
• COMIN1 is the common terminal for inputs 2 to 6.
6
Reference
Reference
Reference
Input/Output Circuit
See "Parallel I/O Interface" (page 5) and "Terminal Block
Interface" (page 5) for common connections.
The overcurrent protective Poly Switch is set to trip at 1 A. Use a
power supply with an output rated 1 A or more.
INPUT
COMIN1
3.3 kΩ
10 kΩ
INPUT
COMIN1
6.2 kΩ
4.7 kΩ
Reference
NOTICE
COMOUT_F+
COMOUT_F-
OUT
Poly Switch
COM
OUT
Poly Switch
COMOUT_F+
COMOUT_F-
OUT
Poly Switch
OUT
Poly Switch
COM