Pin settings, Input/output circuit, Input circuit – KEYENCE CV-X200 Series User Manual

Page 6: Output circuit

background image

6

OUTPUT connector

• Socket block:

MC1.5/9-ST-3.5BK
(Phoenix Contact)

• Suitable wiring

AWG 16 - 28

• Terminal block screw torque

0.25 Nm or less

INPUT connector

• Socket block:

MC1.5/6-ST-3.5BK
(Phoenix Contact)

• Suitable wiring

AWG 16 - 28

• Terminal block screw torque

0.25 Nm or less

Pin Settings

OUTPUT connector

INPUT connector

Input Circuit

Input circuit diagram

Circuit A (F_IN0 to 3 only, EV compatible)

• Max. imposed voltage: 26.4 V
• ON voltage: 10.8 V or greater
• ON current: 3 mA or greater
• OFF voltage: 5 V or less
• OFF current: 1 mA or less

Circuit B (other inputs)

• Max. imposed voltage: 26.4 V
• ON voltage: 10.8 V or greater
• ON current: 2 mA or greater
• OFF voltage: 3 V or less
• OFF current: 0.3 mA or less

Output Circuit

Output circuit diagram (NPN output type)

Circuit C (F_OUT0 to 3 only)

• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or

less

• Residual voltage:

1.4 V or less (50 mA)
1.0 V or less (20 mA)

Circuit D (Other outputs)

• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or

less

• Residual voltage:

1.4 V or less (50 mA)
1.0 V or less (20 mA)

Output circuit diagram (PNP output type, controllers with a "P" at
the end of the part number)

Circuit C (F_OUT0 to 3 only)

• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or

less

• Residual voltage:

1.4 V or less (50 mA)
1.0 V or less (20 mA)

Circuit D (Other outputs)

• Max. imposed voltage: 30 V
• Leakage current: 50 mA
• Leakage current: 0.1 mA or

less

• Residual voltage:

1.4 V or less (50 mA)
1.0 V or less (20 mA)

*1: It is the default assigned value on the terminal where the

signal assignment can be changed. These assignments may
vary if the Global settings have been changed.

*2: For more details about the signal description, see the

"

CV-X

Series User's Manual

"

.

No.

Terminal
name

Signal

Terminal block
display at time
of shipment

Signal
description

*2

Circuit
diagram

1

OUT22

STO

STO

Output timing indicator

D

2

OUT23

OR

OR

Total status output

D

3

F_OUT2

ERROR

*1

ERR

Error output

*1

C

4

F_OUT3

RUN

*1

RUN

Run mode output

*1

C

5

COMOUT1

COMOUT

Common for terminal
block outputs

6

F_OUT0

FLASH 1

FLS1

Strobe light output for
trigger 1

C

7

F_OUT1

FLASH 2

FLS2

Strobe light output for
trigger 2

C

8

COMOUT_
F+

(COMF+)

+ common for terminal
output

9

COMOUT_
F-

(COMF-)

- common for terminal
output

• Power source 0V, COMOUT1, COMOUT_F+, and

COMOUT_F- are all isolated.

• COMOUT1 is the common terminal for output for OUTPUT

connectors 1 to 2.

• COMOUT_F+ and COMOUT_F- are the common terminals for

OUTPUT connectors 3 to 4 and 6 to 7.

No.

Terminal
name

Signal

Terminal block
display at time
of shipment

Signal
description

*2

Circuit
diagram

1

COMIN1

COMIN

Common for terminal
block inputs

2

IN15

PLC

*1

PLC

Command read request
from PLC

*1

B

3

F_IN0

TRG1

TRG1

Trigger 1 input

A

4

F_IN1

TRG2

TRG2

Trigger 2 input

A

5

F_IN2

TEST

*1

TEST

Trial run input

*1

A

6

F_IN3

EXT

*1

EXT

Disable trigger input

*1

A

• Power source 0V and COMIN1 are all isolated.
• COMIN1 is the common terminal for inputs 2 to 6.

6

Reference

Reference

Reference

Input/Output Circuit

See "Parallel I/O Interface" (page 5) and "Terminal Block
Interface" (page 5) f
or common connections.

The overcurrent protective Poly Switch is set to trip at 1 A. Use a
power supply with an output rated 1 A or more.

INPUT

COMIN1

3.3 kΩ

10 kΩ

INPUT

COMIN1

6.2 kΩ

4.7 kΩ

Reference

NOTICE

COMOUT_F+

COMOUT_F-

OUT

Poly Switch

COM

OUT

Poly Switch

COMOUT_F+

COMOUT_F-

OUT

Poly Switch

OUT

Poly Switch

COM