Blue Sky IPN Pro User Manual
Page 14
Blue Sky Energy – IPN-ProRemote
13
¾
When Backlight is on, the IPN-ProRemote can draw up to 100mA from the charge controller. For proper operation of the shunt
current measurement circuits, total voltage difference between the IPN-ProRemote circuit common and the shunt must be kept to
less than
±1.0V when Backlight is on and maximum charge or discharge current is flowing in the system. If long network/power
cables are used, wire size may need to be increased to keep voltage difference between the “COM test point” and “SHUNT –” on
the back of the IPN-ProRemote to within
±1.0V or less at all times. Table 3 below shows wire size for a more conservative
recommended voltage drop limit of 0.50V maximum.
MAXIMUM NETWORK/POWER CABLE LENGTH FOR 0.50V DROP
WIRE GAUGE
AWG
MAXIMUM RECOMMENDED CABLE LENGTH
FEET / METERS
30 AWG
45 / 13.7
28 AWG
73 / 22.2
26 AWG
117 / 35.7
24 AWG
187 / 57.0
22 AWG
295 / 89.9
20 AWG
475 / 144.8
TABLE 3
MOUNTING
¾
CAUTION:. The unit is designed to mount into a standard US duplex wall mount box. It is not watertight and must be protected
from rain, snow and excessive moisture.
DETAILED DIMENSIONAL DRAWING
FIGURE 8
TROUBLESHOOTING GUIDE
SYMPTOM
PROBABLE CAUSE
ITEMS TO EXAMINE OR CORRECT
Display blank
No power
Charge controller not properly powered.
Network cable faulty, not plugged in or cable pins do not swap per Figure 7.
Display turns on, but
battery voltage shows
– –.–V rather than a
number
IPN-ProRemote not communicating with
charge controller
Network cable faulty.
Charge controller or IPN-ProRemote may have locked up, re-boot by momentarily
removing battery and PV power from charge controller.
One charge controller is not set to Master, or more than one charge controller is set
to Master.
Controller-to-controller network cable not wired A-to-A, B-to-B, or wires are open or
short.