beautypg.com

Blue Sky IPN Pro User Manual

Page 14

background image

Blue Sky Energy – IPN-ProRemote

13

¾

When Backlight is on, the IPN-ProRemote can draw up to 100mA from the charge controller. For proper operation of the shunt

current measurement circuits, total voltage difference between the IPN-ProRemote circuit common and the shunt must be kept to
less than

±1.0V when Backlight is on and maximum charge or discharge current is flowing in the system. If long network/power

cables are used, wire size may need to be increased to keep voltage difference between the “COM test point” and “SHUNT –” on
the back of the IPN-ProRemote to within

±1.0V or less at all times. Table 3 below shows wire size for a more conservative

recommended voltage drop limit of 0.50V maximum.

MAXIMUM NETWORK/POWER CABLE LENGTH FOR 0.50V DROP

WIRE GAUGE

AWG

MAXIMUM RECOMMENDED CABLE LENGTH

FEET / METERS

30 AWG

45 / 13.7

28 AWG

73 / 22.2

26 AWG

117 / 35.7

24 AWG

187 / 57.0

22 AWG

295 / 89.9

20 AWG

475 / 144.8

TABLE 3

MOUNTING

¾

CAUTION:. The unit is designed to mount into a standard US duplex wall mount box. It is not watertight and must be protected

from rain, snow and excessive moisture.

DETAILED DIMENSIONAL DRAWING

FIGURE 8

TROUBLESHOOTING GUIDE

SYMPTOM

PROBABLE CAUSE

ITEMS TO EXAMINE OR CORRECT

Display blank

No power

Charge controller not properly powered.

Network cable faulty, not plugged in or cable pins do not swap per Figure 7.

Display turns on, but
battery voltage shows
– –.–V rather than a
number

IPN-ProRemote not communicating with
charge controller

Network cable faulty.

Charge controller or IPN-ProRemote may have locked up, re-boot by momentarily
removing battery and PV power from charge controller.

One charge controller is not set to Master, or more than one charge controller is set
to Master.

Controller-to-controller network cable not wired A-to-A, B-to-B, or wires are open or
short.