Talkaphone CU-8R Area of Rescue Flush Mount Command Unit User Manual
Cu-8r installation instructions
CU-8R Installation Instructions
Copyright 2012 Talk-A-Phone Co. All rights reserved.
Talk-A-Phone Co.
• 7530 North Natchez Avenue • Niles, Illinois 60714-3804
Rev. 12/19/12
Phone 773.539.1100 • Fax 773.539.1241 • [email protected] • www.talkaphone.com
All prices and specifications are subject to change without notice.
Talk-A-Phone, Talk-A-Lert, Scream Alert and WEBS are registered trademarks of Talk-A-Phone Co.
I.
Components
Model CU-8R is shipped with the following components:
QTY
Item
1
Stainless Steel Enclosure
2
Lexan Panels
18
Nuts
1
Wall Mount Style Phone with RJ-11 Cable
1
EC-8 Consolidator
1
Strobe/Siren Assembly
1
Power Source / Uninterruptible Power Source (UPS)
2
Batteries
1
Wiring Harness
2
Low Voltage Relays
1
Door Handle Knob
1
Self-Adhesive Instruction Label
1
Installation and Operation Instruction Manual
II.
Assembly
1)
Remove the five (5) screws holding the cover of the stainless steel enclosure in place.
Carefully remove cover and place in a safe location for re-attachment later. Remove all loose
components that are packed into the enclosure; you will install these in the following steps.
2)
Mount enclosure in wall as described. NOTE: Openings are provided on bottom for providing
power. Determine method of bringing power to enclosure before mounting enclosure in wall.
3)
Mount the Strobe/Siren Assembly on wall in an appropriate location, per the instructions
packed with the Strobe/Siren Assembly.
4)
Complete self-adhesive instruction label by filling in the location of each rescue station in your
system. Remove the label backing and place label well above the phone mounting studs in
the handset compartment.
5)
Plug one end of the RJ11 cable into the back of the telephone, routing the cable through the
back of the phone as indicated on the phone. Mount telephone onto screw/studs in the
accessible telephone section of the enclosure. Route the RJ-11 cable through the hole in the
wall separating the two compartments and plug into the “LOCAL PHONE” Port on the EC-8
Consolidator.
6)
Attach RJ11 connectors from Emergency Phone communication lines to ports 1-8 on EC-8
Consolidator. If a telephone or PBX line is to be used in addition to the phone in the
enclosure, attach phone line to the “TELCO IN” Port on the EC-8. See attached drawing.
7)
Remove the protective covering on the front and back of the two Lexan windows. Carefully
place each window over the studs in the rear of the cover as shown. Secure with twenty (20)
nuts (provided).
8)
Connect 120VAC to the Power Source as indicated “L –N-GND (symbol)”. The green LED will
illuminate.