42

The Average Occupied Heat Set Point displays the

Occupied Heat set point from the Linkage Thermostat.
Average Occupied
Heat Set Point:

Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Occupied Cool Set Point displays the Occu-

pied Cool set point from the Linkage Thermostat.
Average Occupied
Cool Set Point:

Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Unoccupied Heat Set Point displays the Unoc-

cupied heat set point from the Linkage Thermostat.
Average Unoccupied
Heat Set Point:

Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Unoccupied Cool Set Point displays the Unoc-

cupied cool set point from the Linkage Thermostat.
Average Unoccupied
Cool Set Point:

Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Zone Temperature displays the space tempera-

ture from the Linkage Thermostat.
Average Zone
Temperature:

Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Average Occupied Zone Temperature displays the

space temperature from the Linkage Thermostat during occu-
pied periods.
Average Occupied
Zone Temperature: Display Units:

Degrees F (Degrees C)

Display Range:

0.0 to 99.9

Default Value:

0.0

Network Access: None

The Occupancy Status point displays a 1 if occupancy is re-

ported by the Linkage Thermostat. The Occupancy Status
point displays a 0 if occupancy is not reported by the Linkage
Thermostat.
Occupancy
Status:

Display Range:

0, 1

Default Value:

0

Network Access: None

Table 17 — Maintenance

NOTE: Bold values indicate points that can be forced through communications.

DESCRIPTION

VALUE

UNITS

STATUS

FORCE

NAME

Thermostat Control

No

TSTAT

Occupied

Yes

OCCUP

Timed Override in Effect

No

TIMOV

Start Bias Time

0

min

STRTBIAS

Heat

No

HEAT

Cool

No

COOL

IAQ Control

No

IAQCL

Demand Limit

No

DEMLT

Temp Compensated Start

No

TCSTR

IAQ Pre-Occupancy Purge

No

IQPRG

Unoccupied Free Cool

No

NTFCL

Fire Shutdown

No

FIRES

Linkage Control

No

DAVCL

Field/Startup Test

No

FIELD

Heat Submaster Ref

40.0

dF

SHSR

Cool Submaster Ref

150.0

dF

CCSR

Economizer Submaster Ref

120.0

dF

ECONSR

Economizer Submastr Gain

0.00

ECONGN

Compressor Starts

0.00

CMPST

Compressor 1 Runtime

0.00

HOURS

CM1RT

Compressor 2 Runtime

0.00

HOURS

CM2RT

Supply Fan Runtime

17.00

HOURS

FANRT

Linkage Thermostat

Linkage Status

2

LINKSTAT

Supervisory Element

0

SUPE-ADR

Supervisory Bus

0

SUPE-BUS

Supervisory Block

0

BLOCKNUM

Average Occ Heat Setpt

0.0

dF

OCLOSTPT

Average Occ Cool Setpt

0.0

dF

OCHISTPT

Average Unoc Heat Setpt

0.0

dF

UNLOSTPT

Average Unoc Cool Setpt

0.0

dF

UNHISTPT

Average Zone Temp

0.0

dF

AZT

Average Occ Zone Temp

0.0

dF

AOZT

Occupancy Status(1=occ)

1

OCCSTAT