IAQ PRE-OCCUPANCY PURGE — Indicates that the pre-
occupancy purge mode is currently active.
IAQ
Pre-occupancy
Purge:

Display Range:

No/Yes

Default Value:

No

Network Access:

Read Only

UNOCCUPIED FREE COOLING — Indicates that unoccu-
pied free cooling is in effect.
Unoccupied Free
Cooling:

Display Range:

No/Yes

Default Value:

No

Network Access:

Read Only

FIRE SHUTDOWN — Indicates in a sensor mode that the
Fire shutdown input has been sensed. This will cause the
supply fan and heating and cooling to be turned off also.
Fire Shutdown:

Display Range:

No/Yes

Default Value:

No

Network Access:

Read/Write

LINKAGE CONTROL — Indicates if the controller is
receiving linkage communication.
Linkage Control: Display Range:

No/Yes

Default Value:

No

Network Access:

Read/Write

FIELD/STARTUP TEST — This point is used to enable field
test of the controller. When forced to Yes, the controller will
perform a test of all outputs and reset to “NO” at end of test.
The test may be aborted at any time by forcing value to NO.
Field/Startup
Test:

Display Range:

No/Yes

Default Value:

No

Network Access:

Read/Write

HEAT SUBMASTER REFERENCE — When in sensor
mode, the Heat Submaster Reference point displays the supply
air temperature calculated by the heating PID loop. This value
is compared to the actual supply air temperature to determine
the number of required stages. When in the thermostat mode,
the value displayed is zero.
Heat Submaster
Reference:

Display Units:

Degrees F (Degrees C)

Display Range:

40.0 to 150.0

Default Value:

40

Network Access: Read Only

COOL SUBMASTER REFERENCE — The Cool Submas-
ter Reference point displays the supply air temperature calcu-
lated by the cooling PID loop when in sensor mode. This value
is compared to the actual supply air temperature to determine
the number of required stages. When in the thermostat mode,
the value displayed is zero.
Cool Submaster
Reference:

Display Units:

Degrees F (Degrees C)

Display Range:

40.0 to 150.0

Default Value:

150

Network Access: Read Only

ECONOMIZER SUBMASTER REFERENCE — This point
displays the supply air temperature determined by the
Economizer PID calculation.
Economizer
Submaster
Reference:

Display Units:

Degrees F (Degrees C)

Display Range:

48 to 120

Default Value:

120

Network Access:

Read Only

ECONOMIZER SUBMASTER GAIN — Displays the cur-
rent Submaster gain multiplier in use to calculate the econo-
mizer damper position. At temperatures below 45 F this
number will decrease to slow the rate of movement of the
economizer damper.
Economizer
Submaster Gain: Display Range:

–20 to 20

Default Value:

–5.5

Network Access: Read Only

COMPRESSOR STARTS — Displays the total number of
compressor starts.
Compressor
Starts:

Default Value:

0

Network Access: Read Only

COMPRESSOR 1 RUN TIME — Displays the number of
run hours of compressor no. 1.
NOTE: The clock must be set for run times to accumulate.
Compressor 1
Run Time:

Display Units:

Hours

Default Value:

0

Network Access: Read Only

COMPRESSOR 2 RUN TIME — Displays the number of
run hours of compressor 2.
NOTE: The clock must be set for run times to accumulate.
Compressor 2
Run Time:

Display Units:

Hours

Default Value:

0

Network Access: Read Only

SUPPLY FAN RUN TIME — Displays the number of run
hours of the supply fan.
NOTE: The clock must be set for run times to accumulate.

This is not the same timer used for the filter status. A sepa-

rate timer is used to keep track of the run hours since the last
filter change.
Supply Fan
Run Time:

Display Units:

Hours

Default Value:

0

Network Access: Read Only

LINKAGE THERMOSTAT — The following Linkage Ther-
mostat points display the standard values received from a
Linkage Thermostat (if one is being used to provide space
temperature, set point and occupancy information).
Linkage
Status:

Display Range:

0 to 3

Default Value:

2

Network Access: None

The Supervisory Element displays the address of the device

sending the linkage supervisory table to the PremierLink™
controller.
Supervisory
Element:

Default Value:

0

Network Access: Read Only

The Supervisory Bus displays the bus number of the device

sending the linkage supervisory table to the PremierLink
controller.
Supervisory Bus: Default Value:

0

Network Access: Read Only

The Supervisory Block displays the block or table

number of the linkage table occurrence in the supervisory
device. Some linkage supervisory devices may contain
more than one linkage table for different air sources.

Supervisory
Block:

Default Value:

0

Network Access: Read Only