Economizer with Johnson 4 to 20 mA Actua-
tor —

The PremierLink Controller can be connected to an

economizer that uses a Johnson 4 to 20 mA actuator.
DRIVE

DIRECTION

The actuator drive direction is

dependent upon the position of Switch 3 and the spring return
direction. See Table 5. The actuator is factory set for Direct
Acting (DA) operation with Switch 3 in the DA position. An
increasing control signal drives the actuator away from the
spring return position in DA mode. The actuator should be
installed in the DA mode so damper will close automatically
on power shut down.

If Reverse Acting (RA) operation is desired, move Switch 3

to the RA position. An increasing control signal drives the
actuator toward the spring return position in RA mode.
SWITCH SELECTION — The type of input control signal is
determined by the position of Switch 5. With Switch 5 in the
VDC position (factory setting), the signal is DC voltage. With
Switch 5 min the mA position, the input signal changes to
current input. See Fig. 28 and Table 6. The switch should be set
to mA for use with PremierLink controller.

NOTE: To change the factory setting, use a

1

/

8

-in. (3-mm)

flat-blade screwdriver to position the mode switch to the alter-
nate setting.

Table 5 — Actuator Drive Direction Settings

LEGEND

Table 6 — Mode Selection Information

NOTE: The 6 to 9 VDC setting of Switch 1 overrides switch 4.

WIRING (See Fig. 29-30B) — The wires for power and
signal transmission from PremierLink to economizer are field-
supplied. To connect the Economizer Johnson Actuator to
PremierLink controller, connect the pink wire on actuator to
purple wire on PremierLink J9-1. See Fig. 30A.

For the Belimo Actuator, connect the white wire on the ac-

tuator to J9-1 on the PremierLink controller. See Fig. 30B.
NOTE: To retrofit PremierLink Controller to older 4 to 20 mA
actuator, connect the red wire on the actuator wire harness to
the purple wire on the PremierLink J9-1. Connect the yellow
and white wires from the actuator wire harness to the 24-volt
AC transformer on equipment. See Fig. 29.

POSITION OF

SWITCH 3 AND THE

DIRECTION OF

SPRING RETURN

DRIVE

DRIVE DIRECTION

WITH A MINIMUM

INPUT SIGNAL

DRIVE DIRECTION

WITH A MAXIMUM

INPUT SIGNAL

DA/CCW

CCW

CW

RA/CCW

CW

CCW

DA/CW

CW

CCW

RA/CW

CCW

CW

CCW — Counterclockwise
CW

Clockwise

DA

Direct Action

RA

Reverse Action

MODE

SWITCHES

SWITCH FUNCTIONS

FACTORY

SETTINGS

5

VDC or mA

VDC

4

0 to 10 VDC (0 to 20 mA or

2 to 10 VDC (4 to 20 mA)

0 to 10

3

Direct Acting (DA) or

Reverse Acting (RA)

DA

2

FIXED or AUTO

FIXED

1

— or 6 to 9 VDC

IMPORTANT: Make sure the common side is grounded
for both the PremierLink power and the actuator power.
This is especially important if separate transformers are
used.

24 VAC

SENSOR

MIN.
POS

TR

P1

P

T1

T

TR1

24 VAC

TRANSFORMER

Q769B

ADAPTER

2

1

-

+

+

-

+

+

-

-

LOOP

ISOLATOR

PREMIERLINK

CONTROL

J9

M7415

ACTUATOR

24 VAC

SENSOR

MIN.
POS

TR

P1

P

T1

T

TR1

24 VAC

TRANSFORMER

(SEPARATE,

FIELD-SUPPLIED)

500 OHM
RESISTOR

2

1

-

+

+

-

PREMIERLINK

CONTROL

J9

M7415

ACTUATOR

Q769C

ADAPTER

Fig. 26 — PremierLink™ Control Wiring to

Q769B Adapter and Actuator

Fig. 27 — PremierLink Control Wiring to

Q769C Adapter and Actuator

5 4 3 2 1

VDC

0-10

DA

FIXED

mA
2-10

RA

AUTO
6-9

MOVE TO LEFT
FOR 4-20mA CONTROL
WITH PREMIERLINK
CONTROLLER

Fig. 28 — Position of Actuator Mode Switches

(Factory Default)