1. Infeed Safety Barrier - Test Daily - Test the bar by starting the machine and then pushing the
barrier so that the bottom edge swings back 1-2 inches. The machine must shut down in this
travel.
2. Left Front E-Stop - Test by starting the machine and then pressing the button. The machine
must stop.
3. Right Front E-Stop - Test by starting the machine and then pressing the button. The machine
must stop.
4. Left Rear E-Stop - Test by starting the machine and then pressing the button. The machine
must stop.
5. Right Rear E-Stop - Test by starting the machine and then pressing the button. The machine
must stop.
6. Access Cover Interlocks - Open each cover and make certain that the machine stops when
the cover is opened. Tapped, bypassed, or otherwise nonfunctional switches must be cor-
rected. Switches are located on each roll access cover and on the electrical control cabinet.
7. Electrical Panel Disconnect - Check that the disconnect is complete, the switch head is func-
tional and the lockout operates correctly. Check that the trip level of the disconnect is set
properly (if equipped) and record the setting.
8. Main Stop Button - Right front panel - Test by pushing the button when the machine is
running. All functions of the machine should stop except the pump if the pump mode switch
is in the Automatic position.
9. Main Temperature Control - Check that the control’s process temperature matches the Limit
and Pump shutdown controls within 2
o
C or 10
o
F when the machine is warmed up and no
goods have been fed for several minutes. Make sure the temperature reading is not jumpy
or otherwise unstable.
10. Temperature Limit Control – Check that the control’s process temperature matches the Main
and Pump shutdown controls within 2
o
C or 10
o
F. Make sure the temperature reading is not
jumpy or otherwise unstable. Make sure that the setpoint cannot be changed by pushing the
up and down buttons.
11. Pump Shutdown Control – Check that the control’s process temperature matches the Limit
and Main controls within 2
o
C or 10
o
F. Make sure the temperature reading is not jumpy or
otherwise unstable. Verify that the pump shuts down when the machine cools below the
setpoint.
12. Temperature High Limit Lockout - Unlock the high limit control and change the setpoint to
some number below the process temperature or carefully touch a jumper to wire numbers 1
and 102 located on the rear of the control. The machine should lock out the burner operation
and the Temperature Limit Lamp must light. Power the machine down with the main branch
disconnect (external to the machine) - The machine must remain locked out when power is
restored. If the lockout setpoint was changed, restore it to its original valve and relock the
control.